Power network transducer P43 is designed to measure 3-phase (three or four-wire systems) power network parameters. Two parameter values are converted into analog output signal -20...+20 mA. Other parameter values are sent over RS-485 or USB ports. All parameter min and max values are measured. Data refresh interval is less than 1 s. Output signals are isolated from input and supply. Two programmable alarm outputs. Pulse (passive) output OC can be used for energy accounting. Mounted on 35 mm rail.
- Measuring ranges:
- current 1/5 A L1...L3: 0,02...6 A
- voltage L-N/L-L: 2,9...276/ 10...480 V
- frequency: 45,00...66 Hz
- active power: -1,65 kW...1,4 W...1,65 kW
- reactive power: -1,65 kvar...1,4 var...1,65 kvar
- apparent power: 1,4 VA...1,65 kVA
- power factor: -1...0...1
- active energy: 0...99 999 999,9 kWh
- sum energy: 0...99 999 999,9 kvarh
- Consumed power: ≤ 6 VA
- Transformation coefficients: Ku = 1...4000, Ki = 1...10000
- Supply: 85...253 VDC or AC 40...400 Hz
- Ambient temperature: -10...23...+55 °C
More on power network transducer P43 on Lumel website [EN]
P43 datasheet [EN]