This website uses cookies in order to provide better service. By using this website further you accept with this policy.
Product groups

Ограничитель перенапряжения

Ограничитель перенапряжения
Показать:
Сортировка:

Applications:

Surge protection for 2 pair lines or 4 single lines with common reference potential in the data, signal and communication systems: 0-20 mA, 4-20 mA current loop, TTY 4-20 mA, TTY, TTL, V24 (RS232C), high-frequency transmission system.

Specifications:

  • ANSI / IEEE C62.41 category: B, C
  • Rated operating voltage Un 24 V DC
  • Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
  • Rated load current at 25°C IL 1 A
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • D1 current impulse (10/350 μs, per line) 2,5 kA
  • Voltage protection level Up:
    • at In, C2 (8/20 μs, line-line, line-PG) ≤ 55 V
    • at C3, 1 kV/µs (line-line, line-PG) ≤ 48 V
  • Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019

Applications:

surge protection for 2 pair lines of closed circuit (loops) in the data, signal and communication systems: 4-20 mA current loop, analog/digital communication, RS485, RS422 (V11) interface, high-frequency bus system, 2 wires video transmission system.

Specifications:

  • ANSI / IEEE C62.41 category: B, C
  • Rated operating voltage Un 24 V DC
  • Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
  • Rated load current at 25°C IL 1 A
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • D1 current impulse (10/350 μs, per line) 2,5 kA
  • Voltage protection level Up:
    • at In, C2 (8/20 μs, line-line) ≤ 55 V
    • at In, C2 (8/20 μs, line-PG) ≤ 500 V
    • at C3, 1 kV/µs (line-line) ≤ 48 V
    • at C3, 1 kV/µs (line-PG) ≤ 600 V
  • Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019

Applications:

  • For protecting low voltage equipment against lightning and surge damages
  • For installation in conformity with the lightning protection zones concept at LPZ 0-1
  • Designed according to IEC 61643-11:2011

 

Specifications:

  • Category IEC / EN / VDE: class II+III / type 2+3 / C+D
  • Max. continuous operating voltage Uc 275 V AC
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • Voltage protection level Up ≤ 1,5 kV
  • Max. backup fuse 125 A

RSP-E25-... is a Class I+II SPD for surge and lightning protection of low-voltage power supply systems, especially in high-risk exposure areas or building entrances in LPZ 0-2 (IEC 62305-4), protecting against damage caused by direct or nearby lightning strikes; suitable for use in main distribution boards.

  • IEC / EN / VDE category: Class I+II / Type 1+2 / B+C
  • Application: main distribution boards (MB)
  • Power networks: TT, TN-S, TN-C
  • Protection modes: L-N, N-PE
  • Protective elements: MOV, MOV+GDT
  • Enclosure: modular (replaceable module)
  • Mechanical status indicator: green/red flag
  • Compliant with standards: IEC/EN 61643-11:2011, IEC 60364-4-53, IEC 62305, CE, RoHS
Loading...