- Thermosetting cabinet with double doors. The cabinet dimension: 600 x 500 mm (max 2x 5,5 kW) or 800 x 600 (max 2x 7,5 kW; ... max 2x 22 kW).
- Plinth or foundation for fixing the cabinet.
- PLC controller with a display that changes the backlight depending on operating mode.
- Program saved in the controller and on the SD card, enabling transferring the program to another controller in the event of a failure.
- Router equipped with a 2G / 3G / 4G / LTE modem, 1 LAN 10 / 100 Mb/s port and radio module in the 802.11 b/g/n standard, supporting MIMO 2x2.
- Failure signal light on the outside of the cabinet.
- Generator-network switch.
- 32A 5p generator socket.
- Electric shock protection (residual-current circuit breaker)
- Overvoltage protection (class C surge arrester)
- Overcurrent protection.
- Protection against phase loss and phase unbalance with adjustable response thresholds.
- Overload protection for each pump (PKZM0 motor switch – 2 pcs).
- Contactors (2 pcs).
- Pump operation switch (auto / OFF/manual)
- Fan with thermostat.
- Condensation heater with thermostat.
- Service socket for 230 V rail.
- 24V DC power supply.
- Cable glands for tight connection of wires.
- Buffer battery.
- Operating range: from -40 °C to +60 °C.
Service and control functions
- Remote access to the PLC controller settings.
- Setting pump start and stop levels.
- Setting pump running times for performance diagnostics (e.g. 3 unsuccessful tries of pumping within a given timeframe cause sending of the information about reduced performance).
- Hydrostatic level probe range can be set.
- Possibility to set SMS notification delay for such parameters as: no power/power return, high/low level, level probe failure, pump failure.
Additional equipment
- 7” operator panel.
- Pump current measurement during operation.
- Soft-start (above 5,5 kW as standard).
- Open door alert.