- Temperature measurement range: -20...+60 °C
- Humidity measurement range: 0...100 %RH
- Pressure measurement range: 600...1100 hPa
- CO2 concentration measurement range: 0...5000 ppm
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: 1 s...24 h
- Internal sensors
- GSM modem (GPRS)
- SMS and JSON messages can be sent via GPRS data connection
- Messages can be sent on alarms and periodically
- Data can be transferred to PC via USB-C interface
- Calibration certificate of manufacturer included
- Ambient temperature: -20...+60 °C
- Supply: 5200 mAh LiIon battery
- Protection class: IP20
- Warranty: 3 years
- Universal air and environment quality sensor E2-CO2-series measures CO2 (carbon dioxide) level, temperature, humidity, pressure, sound level, ambient light (LUX). Transmits instant values, average hourly values, and average 24-hour values
- Communication: wM-BUS EN13757-3/4:2013, complies OMS 4.0.2
- Modes: C1-A/B, T1 or S1 (selectable on order)
- Measurement ranges
- Temperature: -40…85 °C
- Humidity: 0…100 % RH (non-condensing)
- CO2: 0…5000 ppm (0…55 °C)
- LUX: 0,01…83000 LUX at same frequency as the human eye
- Absolute pressure: 20…100 kPa
- Sound level: 20…90 dBa at 850 Hz
- Measurement accuracy
- Temperature: ± 0,2 at +5…+60 °C; ± 0,5 at -20…+85 °C
- Humidity: ± 2 % RH at 20…80 % RH; ± 3 % RH at 10…90 % RH; ± 3,5 % RH at 0…100 % RH
- CO2: ± (50 ppm + 3%)
- LUX: 4 %
- Pressure: 0,4 kPa
- CO2 sensor calibrates every 20 days
- Warnings about low battery, CO2 sensor malfunction, calibration not performed yet
- Transmission interval: every 90 seconds
- Measured values sample interval: every 6 minutes
- LED and sound indication about CO2 exceeded limit
- Device has 2 antennas for maximum range in both vertical and horizontal directions
- Power supply: 2 x ER18505 3.6 V Li-SOCI2 battery pack (8200 mAh)
- Up to 14 years battery lifetime, standard configuration and operating temperature
TSM400-1-CP is a multi-parameters sensor that supports the 1-Wire protocol. The sensor measures the concentration of carbon dioxide and atmospheric pressure.
- CO2 measurements range: 400…5000 ppm
- Accuracy: ± (40 ppm + 5 %)
- Resolution: 1 ppm
- Calibration: manual
- Pressure measurements range: 10…1200 hPa
- Accuracy (min): ±1.5 (25°C, 750 hPa)
- Accuracy (max): ±2.5 (-20 °C to + 85 °C, 300…1100 hPa)
- Resolution: 1 hPa
- Operating temperature range: -20…+60°C
- Operating relative humidity range: 5…95% (non-condensing)
- Ingress protection: IP20
- Operating voltage range: 4,5…26 VDC
- Stable long-life metal-oxide gas sensor
- Range 0...100 % LEL (0...2,5 % vol.) C2H2
- Resolution 0,1 % LEL (25 ppm) C2H2
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Attached or remote sensor
The SV600 Fixed Acoustic Imager enables users to continuously detect, locate and visualize unheard and unseen air and gas leaks or changes in sound signatures before they become costly problems.
- 64 MEMS digital microphones for image of leaks
- Powerful processor for onboard real time processing: Sound classification, Frequency filtering, dB values and sound intensity mapping, Event triggering
- Measuring distance: 3…15 m
- Integrated visual light camera
- The SV600 can be mounted on moving applications – including as a Boston Dynamics Spot
- Can be mounted close to any equipment or asset, to any area of the production line, or where human access is restricted or dangerous
- Option for IO support through fieldbus coupler
- Integration: HTTP REST API, Modbus
- Operating temperature: -20…+50 °C
- Protection class: IP54
- Communication and power supply: Ethernet RJ45, POE IEEE 802.3at
- Long-life MOS or electrochemical gas sensor
- Range 0....1000 ppm NH3
- Resolution 1 ppm NH3
- Outputs 4...20 mA / 0...10 V, RS-485
- Stable long-life metal-oxide gas sensor
- Range 0....1000 ppm NH3
- Resolution 1 ppm NH3
- Default alarms at 25 ppm / 35 ppm NH3
- Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
- Electrochemical gas sensor
- Range: 0...100, 0...300, 0...1000, (0...10000 on request) ppm NH3
- Resolution: 1 / 2 / 5 ppm NH3
- Sensor lifetime: > 2 years
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -10...+50 °C
- Supply: 11..30 VDC / 24 VAC or 90...265 VAC
- Metal-oxide gas sensor
- Range: 0...1000 ppm NH3
- Resolution: 1 ppm NH3
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -40...+50 °C / 15...90 %RH
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Analog gas detector MC for connection to DGC, MSC, WSB or any compatible gas detector
- Reliable self-monitoring: Integrated watchdog
- Precise signal: 4–20 mA (2–10 V) output for easy system integration
Carbon dioxide (CO2) and temperature transmitter with a display CDT2000 Duct. The device is designed for measurement of air parameters in ventilation channels.
- CO2 range 400...2000 ppm
- Temperature range 0...50 °C
- To measure carbon dioxide and temperature in air and neutral gases ranges 0…5000 ppm, 0...50 °C
- Configuration with keypad or software: measuring ranges, units, outputs settings
- Optional with display or without display
- Galvanic isolation all the ways
- On request range increase up to 0...20 000 ppm
- To measure carbon dioxide in air and neutral gases range 0…5000 ppm
- Configuration with switches or software: measuring ranges, outputs settings
- Optional with display or without display
- Ambient and duct models. Duct model available only without display
Carbon dioxide (CO2), temperature and humidity transmitter with a display CDT2000.
- Carbon dioxide (CO2) range: 400...2000 ppm
- Humidity range: 0...100 %
- Temperature range: 0...50 °C
- Stable long-life optical NDIR gas sensor
- Range 400...5 000/10 000/50 000 ppm CO2
- Resolution 10 ppm CO2
- Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
- Remote probe option
- Stable long-life optical NDIR gas sensor
- Range 400...5 000/10 000/50 000 ppm CO2
- Resolution 10 ppm CO2
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Remote probe option
- NDIR gas sensor
- Range: 0...10 000 ppm CO2
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: 0...+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC as options
- NDIR gas sensor
- Range: 0...50 000 ppm CO2 (up to 100 % CO2 on request)
- Resolution: 0.01 % vol.
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -25…+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
Carbon dioxide transmitter CMT is designed for CO concentration measurement. The transmitter is used to control interior ventilation systems.
- CO range 0...300 ppm
- Electrochemical (CO) and optical NDIR (CO2) gas sensors
- Range: 0...100 ppm CO, 0...10000 ppm CO2
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Operating temperature: -20...+50 °C
- Supply: 24 VDC/VAC
- Protection class: IP65
- Electrochemical gas sensors
- Range: 0...100 ppm CO, 0...20 ppm NO2
- Resolution: 1 ppm CO, 0,1 NO2
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Operating temperature: -20...+50 °C
- Supply: 24 VDC/VAC
- Protection class: IP65
- Stable long-life electrochemical gas sensor
- Range 0....1000 ppm CO
- Resolution 1 ppm CO
- Default alarms at 25 ppm / 35 ppm CO
- Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
- Stable long-life electrochemical gas sensor
- Range: standard 0....200 ppm CO, maximal 0...1000 ppm CO
- Resolution 1 ppm CO
- Default alarms at 25 ppm / 125 ppm CO
- Outputs 2 x relays with switch-over contacts
- Visual and acoustic alarms
- Long-life electrochemical cell
- Range 0....1000 ppm CO
- Resolution 1 ppm CO
- Outputs 4...20 mA / 0...10 V, RS-485
- Stable long-life electrochemical gas sensor
- Range: 0...200 or 0...1000 ppm CO
- Resolution: 1 ppm CO
- Outputs 2 x relays with switch-over contacts
- UART digital interface
- Visual and acoustic alarms
- Magnetic key switching
- Electrochemical gas sensor
- Range:
- -- 0…300 ppm CO
- -- 0...1000 ppm CO
- Resolution: 1 ppm CO
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -20...+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Addressable digital gas detection system (Sensor-Board SB) for combustible, toxic and refrigerant gases.
- Communication: RS-485 interface for stable and secure system networking
- Precise Detection: High accuracy thanks to digital signal processing
- Easy maintenance with X-Change: Plug & Play systems for fast, convenient service
- Robust Design: Reliable with IP65 even under extreme conditions
- Stable long-life electrochemical cell
- Range 0...20 ppm Cl2
- Resolution 0,02 ppm Cl2
- Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
- Default alarm set-points 0,5 ppm/1 ppm Cl2
- Remote probe option
- Stable long-life electrochemical cell
- Range 0...20 ppm Cl2
- Resolution 0,02 ppm Cl2
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Remote probe option
- Electrochemical gas sensor
- Range: 0...10 ppm Cl2
- Resolution: 0,1 ppm Cl2
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -20...+50 °C
- Supply: 11...30 VDC (default), 24 VAC or 90...265 VAC
- CO2 concentration measurement range: 0...10 000 / 50 000 ppm
- External sensor cable length 1 / 2 / 4 m
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: 10 s...24 h
- Calibration certificate included
- LED, acoustic alarms
- LCD screen
- Data can be transferred to PC via USB-C interface
- Operating temperature: -20...+60 °C
- Supply: battery
- Protection class: IP54
- Warranty: 3 years
- Measures carbon dioxide concentration in air
- Measurement range: 0...2000 ppm
- Operating temperature: -30...60 °C
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 15 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
- Measures carbon dioxide concentration in air
- Measurement range: 0...10000 ppm
- Operating temperature: -30...80 °C
- Cable length: 1 / 2 / 5 / 10 m
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 15 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
- Measures carbon dioxide concentration in air
- Duct mount
- Measurement range: 0...2000 ppm
- Operating temperature: -30...60 °C
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 15 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
- Measures carbon dioxide concentration in air, temperature, humidity
- Calculates dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
- Measurement ranges: 0...2000 ppm, -30...+80 °C, 5...95 %RH
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 2 s; CO2: 15 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
- Measures carbon dioxide concentration in air, temperature, humidity
- Calculates dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
- Measurement ranges: 0...10000 ppm, -30...+105 °C, 5...95 %RH
- Temperature and humidity sensor cable length: 1 / 2 / 4 m
- Carbon dioxide concentration sensor cable length: 1 2 / 5 / 10 m
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 2 s; CO2: 15 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
- CO2 concentration measurement range: 0...10 000 ppm
- Output: 4...20 mA
- Programmable
- External probe cable length: 1 / 2 / 4 m
- LCD display
- Calibration certificate included
- Ambient temperature: -30...+80 °C
- Supply: 9...30 VDC
- Protection class: IP65
- Warranty: 3 years
SM400-4-CPTH is a multi-sensor that supports MODBUS RTU protocol over the RS-485 interface. The sensor measures CO2 concentration, humidity, temperature and barometric pressure. Suitable for environmental quality monitoring, indoor air, smart ventilation systems, restaurants and breweries CO2 level and CO2 leakage control.
- Changeable bitrate and other communication parameters
- Non-volatile memory for all setting
- Temperature measurement range: -20 to 60°C
- Accuracy (min): ±0.4 °C (in -10 to +60°C range)
- Accuracy (max): ±0.6 °C (in -20 to +60°C range)
- Resolution: 0.1 °C
- Relative humidity measurement range: 10 to 90% (non-condensing) *
- Accuracy (min): ±3.0 %RH (in 20 to 80 %RH range)
- Accuracy (max): ±5.0 %RH (in 10 to 90 %RH range) *
- Resolution: 0.1 %RH
- CO2 measurements range: 400…5000 ppm
- Accuracy: ± (40 ppm + 5 %)
- Resolution: 1 ppm
- Calibration: Automatic, if the sensor is exposed to fresh air for more than 30 minutes
- Pressure measurements range: 10 to 1200 hPa
- Accuracy (min): ±1.5 (25°C, 750 hPa)
- Accuracy (max): ±2.5 (-20°C to + 85°C, 300 to 1100 hPa)
- Resolution: 1 hPa
- Ingress protection: IP20
- Operating voltage range: 4.5…26 VDC
- For methane, butane, propane and hydrogen
- Stable long-life metal-oxide gas sensor
- Range 0...100 % LEL
- Resolution 0,1 % LEL
- Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
- Default alarms at 20 / 50 % LEL
- For methane, LPG, hydrogen and acetylene
- Can be calibrated for metane, propane and butane
- Stable long-life metal-oxide gas sensor
- Range 0...100 % LEL
- Resolution 0,1 % LEL
- Outputs 2 x relays with switch-over contacts
- Default alarms at 10 / 25 % LEL
- For methane, butane, propane and hydrogen
- Stable long-life metal-oxide gas sensor
- Range 0...100 % LEL
- Resolution 0,1 % LEL
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- For methane, LPG, hydrogen and acetylene
- Can be calibrated for methane, butane, propane, acetylene and hydrogen
- Stable long-life metal-oxide gas sensor
- Range: 0...100 % LEL
- Resolution: 0,1 % LEL
- Outputs 2 x relays with switch-over contacts
- Default alarms set-points 10 / 25 % LEL
- UART digital interface
- Alarms: blinking LED, 85 dB buzzer
- Metal-oxide gas sensor
- Detected gases: hydrogen, methane, acetylene, propane, butane
- Standard calibration: methane
- Range: 0...100 % LEL
- Resolution: 0,1 % LEL
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -40...+70 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Applications of flue gas analyzer Si-Ca 130: boilers, burners, water heaters and furnaces
- Detectable gases: O2, CO, CO(H2), CO2, NO, Low NO, NOx, Low NOx
- Up to three gas sensors
- CO measurement up to 8000 ppm
- Other measurement parameters: flue temp., air temp., differential temp., pressure / draft, excess air, combustion efficiency, combustion efficiency (condensation), stack gas velocity
- Color graphical touchscreen for control
- Communication: USB, Bluetooth (mobile App), remote printer
- Measurement storage: 2000 data points + smartphone and PC
- Predictive maintenance with estimated sensor life and calibration reminders
- Protection class: IP42
- Power supply: Rechargeable battery, Li-Ion 5100 mA/h 3.6 V (8 hours working time)
- Operating temperature: -5…+45 °C
- Sensor protection by pump stopping
- Warning- and Sensor-Board WSB for digital and analog sensor technology for the precise detection of combustible, toxic and refrigerant gases.
- Versatile alarm function: Alarm and fault relays (30 V)
- Intelligent interfaces: RS-485 interface with DGC or Modbus protocol
- Precise signal transmission: 4–20 mA input and output for reliable communication
- Flexible: Connection of up to 3 sensors (2 digital)
- Stable long-life electrochemical gas sensor
- Range 0...10 / 0...200 / 0...1500 ppm C2H4
- Resolution 0,1 / 1 / 5 ppm C2H4
- Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
- Stable long-life electrochemical gas sensor
- Range 0...10 / 0...200 / 0...1500 ppm C2H4
- Resolution 0,1 / 1 / 5 ppm C2H4
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Attached or remote sensor
- Electrochemical gas sensor
- Range: 0...10 / 0...200 / 0...1500 ppm C2H4
- Resolution: 0,1 / 1 / 1 ppm C2H4
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -20...+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Electrochemical gas sensor
- Range: 0...20 / 0...100 ppm C2H4O
- Resolution: 0,1 / 1 / 5 ppm C2H4O
- Analog output: 2 x 4...20 mA / 0a...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -20...+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
Multifunctional indoor climate sensor AERASGARD RFTM - LQ - PS - CO2 - Modbus with with LCD display.
- Temperature measuring range / deviation: 0…+50 °C / ± 0,2 °C at +25 °C
- Humidity measuring range / deviation: 0…100 % RH / ± 2 % RH (20…80 % RH), at 25 °C, otherwise ± 3 %
- CO2 Measuring range / accuracy: 0…5000 ppm / ± 30 ppm ± 3 % of measured value
- Particulate matter (PM) measuring range / accuracy: 0…50 μg/m³ 0…100 μg/m³ 0…300 μg/m³ 0…500 μg/m³
- Particulate matter (PM) accuracy ± 10 μg/m3 (± 10 % of measured value) at PM 2.5, ± 25 μg/m3 (± 25 % of measured value) at PM 10
- Air quality (VOC) measuring range: 0…100 %
- Data output: galvanically separated RS-485 Modbus RTU interface
- Variants: with / without LCD display
- One sensor covers about 30 m² of room area
- Power supply: 24 V ac/dc (200 mA)
- Standards: CE, EN 61 326, EMC Directive 2014/ 30/ EU, 2014/ 35/ EU