Gas / particle concentration transducers

Gas / particle concentration transducers
Show:
Sort By:
  • Stable long-life metal-oxide gas sensor
  • Range 0...100 % LEL (0...2,5 % vol.) C2H2
  • Resolution 0,1 % LEL (25 ppm) C2H2
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • Attached or remote sensor
  • Long-life MOS or electrochemical gas sensor
  • Range 0....1000 ppm NH3
  • Resolution 1 ppm NH3
  • Outputs 4...20 mA / 0...10 V, RS-485
  • Stable long-life metal-oxide gas sensor
  • Range 0....1000 ppm NH3
  • Resolution 1 ppm NH3
  • Default alarms at 25 ppm / 35 ppm NH3
  • Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
  • Electrochemical gas sensor
  • Range: 0...100, 0...300, 0...1000, (0...10000 on request) ppm NH3
  • Resolution: 1 / 2 / 5 ppm NH3
  • Sensor lifetime: > 2 years
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -10...+50 °C
  • Supply: 11..30 VDC / 24 VAC or 90...265 VAC
  • Metal-oxide gas sensor
  • Range: 0...1000 ppm NH3
  • Resolution: 1 ppm NH3
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -40...+50 °C / 15...90 %RH
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC
  • Analog gas detector MC for connection to DGC, MSC, WSB or any compatible gas detector
  • Reliable self-monitoring: Integrated watchdog
  • Precise signal: 4–20 mA (2–10 V) output for easy system integration

Carbon dioxide (CO2) and temperature transmitter with a display CDT2000 Duct. The device is designed for measurement of air parameters in ventilation channels.

  • CO2 range 400...2000 ppm
  • Temperature range 0...50 °C
  • To measure carbon dioxide and temperature in air and neutral gases ranges 0…5000 ppm, 0...50 °C
  • Configuration with keypad or software: measuring ranges, units, outputs settings
  • Optional with display or without display
  • Galvanic isolation all the ways
  • On request range increase up to 0...20 000 ppm

 

  • To measure carbon dioxide in air and neutral gases range 0…5000 ppm
  • Configuration with switches or software: measuring ranges, outputs settings
  • Optional with display or without display
  • Ambient and duct models. Duct model available only without display

Carbon dioxide (CO2), temperature and humidity transmitter with a display CDT2000.

  • Carbon dioxide (CO2) range: 400...2000 ppm
  • Humidity range: 0...100 % 
  • Temperature range: 0...50 °C
  • Stable long-life optical NDIR gas sensor
  • Range 400...5 000/10 000/50 000 ppm CO2
  • Resolution 10 ppm CO2
  • Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
  • Remote probe option
  • Stable long-life optical NDIR gas sensor
  • Range 400...5 000/10 000/50 000 ppm CO2
  • Resolution 10 ppm CO2
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • Remote probe option
  • NDIR gas sensor
  • Range: 0...10 000 ppm CO2
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: 0...+50 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC as options
  • NDIR gas sensor
  • Range: 0...50 000 ppm CO2 (up to 100 % CO2 on request)
  • Resolution: 0.01 % vol.
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -25…+50 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC

Carbon dioxide transmitter CMT is designed for CO concentration measurement. The transmitter is used to control interior ventilation systems.

  • CO range 0...300 ppm
  • Electrochemical (CO) and optical NDIR (CO2) gas sensors
  • Range: 0...100 ppm CO, 0...10000 ppm CO2
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Operating temperature: -20...+50 °C
  • Supply: 24 VDC/VAC
  • Protection class: IP65
  • Electrochemical gas sensors
  • Range: 0...100 ppm CO, 0...20 ppm NO2
  • Resolution: 1 ppm CO, 0,1 NO2
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Operating temperature: -20...+50 °C
  • Supply: 24 VDC/VAC
  • Protection class: IP65
  • Stable long-life electrochemical gas sensor
  • Range 0....1000 ppm CO
  • Resolution 1 ppm CO
  • Default alarms at 25 ppm / 35 ppm CO
  • Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
  • Stable long-life electrochemical gas sensor
  • Range: standard 0....200 ppm CO, maximal 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Default alarms at 25 ppm / 125 ppm CO
  • Outputs 2 x relays with switch-over contacts
  • Visual and acoustic alarms
  • Long-life electrochemical cell
  • Range 0....1000 ppm CO
  • Resolution 1 ppm CO
  • Outputs 4...20 mA / 0...10 V, RS-485
  • Stable long-life electrochemical gas sensor
  • Range: 0...200 or 0...1000 ppm CO
  • Resolution: 1 ppm CO
  • Outputs 2 x relays with switch-over contacts
  • UART digital interface
  • Visual and acoustic alarms
  • Magnetic key switching
  • Electrochemical gas sensor
  • Range:
  • -- 0…300 ppm CO
  • -- 0...1000 ppm CO
  • Resolution: 1 ppm CO
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -20...+50 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC
  • Addressable digital gas detection system (Sensor-Board SB) for combustible, toxic and refrigerant gases.
  • Communication: RS-485 interface for stable and secure system networking
  • Precise Detection: High accuracy thanks to digital signal processing
  • Easy maintenance with X-Change: Plug & Play systems for fast, convenient service
  • Robust Design: Reliable with IP65 even under extreme conditions
  • Stable long-life electrochemical cell
  • Range 0...20 ppm Cl2
  • Resolution 0,02 ppm Cl2
  • Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
  • Default alarm set-points 0,5 ppm/1 ppm Cl2
  • Remote probe option
  • Stable long-life electrochemical cell
  • Range 0...20 ppm Cl2
  • Resolution 0,02 ppm Cl2
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • Remote probe option
  • Electrochemical gas sensor
  • Range: 0...10 ppm Cl2
  • Resolution: 0,1 ppm Cl2
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -20...+50 °C
  • Supply: 11...30 VDC (default), 24 VAC or 90...265 VAC
  • CO2 concentration measurement range: 0...10 000 ppm
  • Output: 4...20 mA
  • Programmable
  • External probe cable length: 1 / 2 / 4 m
  • LCD display
  • Calibration certificate included
  • Ambient temperature: -30...+80 °C
  • Supply: 9...30 VDC
  • Protection class: IP65
  • Warranty: 3 years
  • For methane, butane, propane and hydrogen
  • Stable long-life metal-oxide gas sensor
  • Range 0...100 % LEL
  • Resolution 0,1 % LEL
  • Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
  • Default alarms at 20 / 50 % LEL
  • For methane, LPG, hydrogen and acetylene
  • Can be calibrated for metane, propane and butane
  • Stable long-life metal-oxide gas sensor
  • Range 0...100 % LEL
  • Resolution 0,1 % LEL
  • Outputs 2 x relays with switch-over contacts
  • Default alarms at 10 / 25 % LEL
  • For methane, butane, propane and hydrogen
  • Stable long-life metal-oxide gas sensor
  • Range 0...100 % LEL
  • Resolution 0,1 % LEL
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • For methane, LPG, hydrogen and acetylene
  • Can be calibrated for methane, butane, propane, acetylene and hydrogen
  • Stable long-life metal-oxide gas sensor
  • Range: 0...100 % LEL
  • Resolution: 0,1 % LEL
  • Outputs 2 x relays with switch-over contacts
  • Default alarms set-points 10 / 25 % LEL
  • UART digital interface
  • Alarms: blinking LED, 85 dB buzzer
  • Metal-oxide gas sensor
  • Detected gases: hydrogen, methane, acetylene, propane, butane
  • Standard calibration: methane
  • Range: 0...100 % LEL
  • Resolution: 0,1 % LEL
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -40...+70 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC
  • Warning- and Sensor-Board WSB for digital and analog sensor technology for the precise detection of combustible, toxic and refrigerant gases.
  • Versatile alarm function: Alarm and fault relays (30 V)
  • Intelligent interfaces: RS-485 interface with DGC or Modbus protocol
  • Precise signal transmission: 4–20 mA input and output for reliable communication
  • Flexible: Connection of up to 3 sensors (2 digital)
  • To measure and data logging: carbon dioxide (0...5000 ppm), temperature (0...50 °C), atmospheric pressure (800...1100 hPa), humidity (0…100 % RH) in air and neutral gases
  • Free software for configuration and data visualization
  • Bluetooth communication for smartphones and tablets (Android and IOS)
  • Safety lock magnetic mounting with inviolability system holder (accessories)
  • Compatible with food industry environment
  • Up to 4 recordable parameters simultaneously
  • Optional calibration certificate
  • Stable long-life electrochemical gas sensor
  • Range 0...10 / 0...200 / 0...1500 ppm C2H4
  • Resolution 0,1 / 1 / 5 ppm C2H4
  • Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
  • Stable long-life electrochemical gas sensor
  • Range 0...10 / 0...200 / 0...1500 ppm C2H4
  • Resolution 0,1 / 1 / 5 ppm C2H4
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • Attached or remote sensor
  • Electrochemical gas sensor
  • Range: 0...10 / 0...200 / 0...1500 ppm C2H4
  • Resolution: 0,1 / 1 / 1 ppm C2H4
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -20...+50 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC
  • Electrochemical gas sensor
  • Range: 0...20 / 0...100 ppm C2H4O
  • Resolution: 0,1 / 1 / 5 ppm C2H4O
  • Analog output: 2 x 4...20 mA / 0a...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -20...+50 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC

Multifunctional indoor climate sensor AERASGARD RFTM - LQ - PS - CO2 - Modbus with with LCD display.

  • Temperature measuring range / deviation: 0…+50 °C / ± 0,2 °C at +25 °C
  • Humidity measuring range / deviation: 0…100 % RH / ± 2 % RH (20…80 % RH), at 25 °C, otherwise ± 3 %
  • CO2 Measuring range / accuracy: 0…5000 ppm / ± 30 ppm ± 3 % of measured value
  • Particulate matter (PM) measuring range / accuracy: 0…50 μg/m³ 0…100 μg/m³ 0…300 μg/m³ 0…500 μg/m³
  • Particulate matter (PM) accuracy ± 10 μg/m3 (± 10 % of measured value) at PM 2.5, ± 25 μg/m3 (± 25 % of measured value) at PM 10
  • Air quality (VOC) measuring range: 0…100 %
  • Data output:  galvanically separated RS-485 Modbus RTU interface
  • Variants: with / without LCD display
  • One sensor covers about 30 m² of room area
  • Power supply: 24 V ac/dc (200 mA)
  • Standards: CE, EN 61 326, EMC Directive 2014/ 30/ EU, 2014/ 35/ EU
  • Suitable for ATEX Zones 2 and 22
  • Electrochemical gas sensor
  • Range: 0...100, 0...300, 0...1000, 0...5000 ppm NH3
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+50 °C
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life pellistor (catalytic bead) sensor
  • Range: 0...15% vol. (0…100% LEL)
  • Resolution: 0.1% vol. or 1% LEL
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -10...+50 °C
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life photoacoustic or optical NDIR sensor
  • Range: 0...10 000 ppm / 0...40 000 ppm / 0...5 % vol (0...100 % on request)
  • Resolution: 1 ppm / 10 ppm / 0.01 % vol. CO2
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+60 °C; 0….100 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range: 0...300 or 0...1000 ppm
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -20...+50 °C; 0….90 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Detected gases: hydrogen, methane, acetylene, propane, butane
  • Default calibration: methane CH4
  • Stable long-life metal-oxide / pellistor sensor
  • Range: 0...100% LEL
  • Resolution: 0,1 / 1 % LEL
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+70 °C; ≤ 95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range: 0...10 / 0...200 / 0...1500 ppm
  • Resolution: 0,1 / 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+50 °C; up to 100 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Detectable gases: R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R-507, R-514a, R-1234ze and similar
  • Stable long-life metal-oxide sensor
  • Range: 0…1000 / 0…2500 ppm
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -30...+60 °C; < 95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range: 0...100 ppm, 0...2000 ppm H2S
  • Resolution: 1 ppm H2S
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+50 °C; 15…90 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life metal-oxide / pellistor sensor
  • Range: 0...100% LEL CH4
  • Resolution: 0,1 / 1 % LEL CH4
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+70 °C; ≤ 95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range: 0…250 ppm
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -30...+50 °C; 15…90 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life optical NDIR sensor
  • Range: 0…1000 ppm
  • Resolution: 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -20...+50 °C; 0…95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC