- Sensor CX-TH measures ambient temperature and humidity
- Communication: wM-BUS EN 13757-3/4:2013, complies OMS 4.0.2
- Measurement ranges
- Temperature: -40…+85 °C
- Humidity: 20…80 % RH (non condensing)
- Measurement accuracy
- Temperature: ± 0,2 °C in the range of 0…65 °C
- Humidity: ± 2 % RH in the range of 20…80 %
- Transmission interval: 60 s…1 hour*
- AES-128 encryption mode 5, profile A, custom KEY
- Power supply: ER14505 3.6V Li-SOCl2 battery (soldered or optional battery holder)*
- 14 years expected, standard configuration and operating temperature
- Operating temperature: 0...+55 °C
- * - T1-mode, 150 seconds, Encryption ON, unique key (individual options should be stated before order)
More about air quality sensors on Lansen website [EN]
CX-TH datasheet [EN]