- Датчик температуры AUREGIS ТJ-1 с соединительным кабелем
- Предназначен для измерения температуры в диапазоне -50°C до 400°C
- Возможны исполнения по требованиям заказчика
- Тип сенсора: PT100, PT1000, K, J, PTC, NTC, Ni120, Ni1000
- Датчик температуры AUREGIS ТJ-4 с соединительным кабелем. Предназначен для измерения температуры в диапазоне -50°C до 400°C
- Возможны исполнения по требованиям заказчика
- Тип сенсора: PT100, PT1000, K, J, Ni120, Ni1000
- Sensor type: RTD (Pt100, Pt1000), TC (K, J)
- Output: RTD (Pt100, Pt1000), TC (K, J), 4...20 mA, 4...20 mA +HART, 0...10 V, RS-485, IO-LINK
- Measuring range: -30 °C ... 250 °C, 550 °C
- Accuracy: Class A or B /cl.2
- Sensor tube:
- Material: Stainless steel AISI304 (1.4301)
- Diameter: Ø6/8/10mm
- Length: 100, 200, 500, 700, 1000mm or on request
- Connection head type: B
- Protection class: IP65
- Electrical connection: 2-wire, 3-wire or on request
- Process connection: G¼”; M20x1,5; G½” or on request
- Various sizes are available depending on customer requirements and drawings
- The temperature sensor TJ-M is designed for measuring the temperature in the capacity ranging from -30°C to 550°C
- The design could be changed according the requirements and drawings of the customer
- Sensor type: Pt100, Pt1000, K, J
- Connection head type: M
- Protection class: IP65
- Designed to be weld-in into pipelines and boilers
- Instrument standard threads (F): G1/2", G1/4"
- Dimensions according to customer's needs
- Case production: solid or welded
- Available materials: 1.4301 (AISI304), 1.4401 (AISI316), 1.4404 (AISI316L)
- Dimension tolerances according to DIN ISO 2768
- Available other materials, threads, flanges and dimensions
- Process flanges according to: EN 1092-1, DIN 2527, ASME B 16.5
- Standard instrument threads (F): G1/2", G1/4"
- Dimensions according to customer's needs
- Case production: welded or solid (flange welded)
- Available materials: 1.4301(AISI304), 1.4401 (AISI316), 1.4404 (AISI316L)
- Dimension tolerances according to DIN ISO 2768
- Available other materials, threads, flanges and dimensions
Solid drilled threaded thermowells, protective cases:
- Protect and extend the lifetime of temperature sensors and thermometers in processing applications
- Facilitate the replacement of sensors
- Allow sensor maintenance without process interruption
A and B connection threads:
G1/4, G1/2, M20x1,5, M10x1, M12x1,5, M20x1,5, G3/4, M16x1,5, M22x1,5,
Spec, G1/2L*
* - left-hand thread
Material: stainless steel-DIN 1.4301 (AISI 304)
Note: other ordering versions possible.
Thermowells protect and extend the lifetime of temperature sensors and thermometers in processing applications where the sensors are not mechanically or chemically compatible with the process environment. Moreover, thermowells facilitate the replacement of sensors and allow sensor maintenance without process interruption.
Electrode level sensor AUREGIS LJ-EB for liquids level measurement. By request sensor can be made with 2 to 5 electrodes with different lengths.
- LJ-EB2 - 2 electrode level sensor
- LJ-EB3 - 3 electrode level sensor
- LJ-EB4 - 4 electrode level sensor
- LJ-EB5 - 5 electrode level sensor
Technical specifications:
- Electrodes: Stainless steel DIN 1.4301 (AISI 304)
- Insulator: Teflon
- Electrode extension: Stainless steel DIN 1.4301 (AISI 304)
- Process connection: Stainless steel DIN 1.4301 (AISI 304)
- Connection head: Aluminum alloy
- Electrode length: Standard – 1000 mm or by request
- Process connection: R1 1/2“
- Process temperature: -30...+180 °C
Vertical, stainless steel, float level sensor with float protection against mechanical impact, designed for level control.
- Material of float: stainless steel AISI 316 SS
- Max. temperature: -30...+105 °C
- Switch rating: 50 VA
- Switching voltage: 230 AC / DC
System is designed to measure width of planar products on conveyor belt. System can be used as a separate module or integrated into production line for process control. It enables to compensate conveyor belt unevenness even if shaft imbalance to axle is present, not affecting measurement accuracy.
If there is no way to measure the product from both sides (i.e. on conveyor belt), one-sided system can be used. In this way the accuracy will depend on evenness of product movement.
Can be conducted without stopping the belt:
- Measure product width
- Detect product curvature
Additional functions:
- Count products
- Measure downtime
- Control processes which influence product width
System consists of following:
- Sensor Instruments high accuracy laser distance sensors
- PLC
- HMI or computer
The AUREGIS LJ-VD4M12 multi-zone floating, stainless steel level relay with standard M12 connector is designed for liquid level measurement and regulation.
- Connection connector: M12 (4 / 8 pins)
- Floats and float holders are customizable (on request)
- Connection thread: G3/4" or larger (on request)
- Switching power: 25 VA
- Switching voltage: 24 V AC/DC
- Process part operating temperature: -30...+105 °C
- Process part: Stainless steel AISI316L
- Protection class: IP65
- Oxygen concentration measuring in air and inert gas mixtures
- Specially developed for use in composting plants
- Measuring range of oxygen concentration: 0,1…25 % (0…100 % range on request)
- Value indicator of measured oxygen concentration
- Output: 4…20 mA analog or bidirectional digital signal (for calibration, operation diagnostic)
- Length and diameter of the sensor protection tube to the handle: 1200 x 30 mm
- Length of the protective tube part to be stuck in the compost heap: ~ 1000 mm
- Material of protective tube: Stainless steel 1.4301
- Housing ambient temperature: -10…+50 °C
- Probe ambient temperature: -10…+100 °C
- Protection class of housing electronic: IP65
- Protection class of probe: IP40
- Rechargeable battery with indication of voltage
- It is possible to connect the sensor to a stationary data processing system
- Penetration temperature sensor TJ-ST
- Sensor type: Pt100, Pt1000
- Accuracy: A or B
- Measuring range: -30 °C...+180 °C
- Measuring part diameter: Ø 4 mm
- Measuring part length: 100 mm
- Material: stainless steel
- Various sizes are available depending on customer requirements and drawings
- Temperature sensor AUREGIS TJ-H with hygienic – food process connection and special welded slot, designed for temperature measurement from -50 to +400 °C
- Temperature sensor construction specially designed for usage in food, pharmaceutical, water extraction and water purification, biotechnology and other industries
- Temperature sensor and slot are made of stainless steel
- Measuring range: from -50°C to 250°C, 400 °C
- Temperature sensor AUREGIS TJ-H with hygienic – food process connection and M12x1 4 pin connector
- Sensor type: RTD (Pt100, Pt1000), TC (K, J)
- Accuracy: A or B
- Measuring range: from -50°C to 400°C
- Sensor tube:
- Length: 100, 180, 200 mm
- Diameter: Ø6/8/10 mm
- Material: stainless steel
- Process connection tread: G1/2
- Transmitter output type: 4...20 mA, 4...20 +HART, 0-10 V, RS-485 other parameters acc. to requirement
- Cable connector: M12x1 4 pin
- Various sizes are available depending on customer requirements and drawings
- Sensor type: Pt100, PT1000, K, J, PTC, NTC, Ni120, Ni1000
- Measurement range: -30...180 °C
- Cable: 2, 3, 4-wire
- Magnetic mounting ring
TJ-1V sensor is convenient for installation on pipes with staples. For HVAC systems.
- Measurement range: -30...+105 °C
- Sensor type: PT100, PT1000, PTC, NTC, Ni1000, TC K
- Sensor measurement material: brass
- Cable of two or three wires with PVC isolation. Cable length: on request
Temperature sensor AUREGIS TJ-PL6 is integrally connected to the cable. Protection from UV
Purpose: solar panels and other surfaces.
- Sensor type: PT100, PT1000, PTC, NTC, Ni1000
- Sensor working temperature range*: -40...+90 °C
- Cable wires*: 3-wire
- Sensor material: aluminum
- Plate diameter / thick: Ø30 mm / 10 mm
- Cable length: according to order
* - we produce according to individual orders
- Temperature sensor with penetration probe, “T” type handle and cable connection head
- Various sizes are available depending on customer requirements and drawings
- Sensor type: Pt100, Pt1000, K, J
- Accuracy class: A or B / cl. 1 or 2
- Measuring range: -30...180 °C or -30...260 °C on request
- Sensor’s tube:
- Material: Stainless steel AISI304 (1.4301)
- Diameter: Ø 6 / 8 / 10 mm
- Length: 100, 200, 500, 700, 1000 mm on request
- The total length of the sensor handle is 220 mm
- Connection head:
- Type: M, B (transducer on request)
- Protection class: IP65
- Sensor type: Pt100, Pt1000, Ni100, Ni1000, others
- Electrical connection:
- A transmitter with output: 4…20 mA, 4...20 mA +HART, 0…10 V, RS-485 or IO-LINK
- 2-wire, 3-wire, a contact terminal
- Measuring range: -40…180 °C (depends on probe)
- Operating temperature (case with transmitter): -40…80 °C
- The sensor TJ-1 is selected according to the individual order
- Mounting box:
- Material: Polystyrene
- Dimensions: 64,4x 88,4x 42,2mm
- Protection class: IP65
- The design could be changed according the requirements and drawings of the customer
- Sensor type: Pt100, Pt1000, Ni100, Ni1000, others
- Electrical connection:
- A transmitter with output: 4…20 mA, 4...20 mA +HART, 0…10 V, RS-485 or IO-LINK
- 2-wire, 3-wire, a contact terminal
- Measuring range: -40…180 °C (depends on probe)
- Operating temperature (case with transmitter): -40…80 °C
- The sensor TJ-4 is selected according to the individual order
- Mounting box:
- Material: Polystyrene
- Dimensions: 64,4x 88,4x 42,2mm
- Protection class: IP65
- The design could be changed according the requirements and drawings of the customer
- Sensor type: Pt100, Pt1000, Ni100, Ni1000, others
- Electrical connection:
- A transmitter with output: 4…20 mA, 4...20 mA +HART, 0…10 V, RS-485 or IO-LINK
- 2-wire, 3-wire, a contact terminal
- Measuring range: -40…180 °C (depends on probe)
- Operating temperature (case with transmitter): -40…80 °C
- The sensor TJ-S is selected according to the individual order
- Mounting box:
- Material: Polystyrene
- Dimensions: 64,4x 88,4x 42,2mm
- Protection class: IP65
- The design could be changed according the requirements and drawings of the customer
The TJ-S temperature sensor is permanently connected to a cable and designed for measuring temperatures from -50°C to 400°C.
Various cable lengths are available.
- Sensor type: PT100, PT1000, NTC, Thermocouples K, J
- Measuring range: -50…+400 °C
- Operating temperature:
- -30...+70 °C (PVC isolation)
- -50...+180 °C (Silicone isolation)
- -50...+400 °C, kabelio -50...+250 °C (Teflon isolation)
- -50...+400 °C, kabelio -50...+400 °C (Fiberglass isolation)
- Cable and connection: 2, 3, 4 wire
- Sensor tube:
- Material: Stainless steel 316 (1.4401)
- Diameter: Ø4 mm
- Length: 120 mm
- Temperature sensor TJ1TE – NTC10k3B HVAC developed for air conditioning devices and heating, ventilation, (HVAC) systems
- Measurement range: -30…+105 °C
- Sensor: NTC; Rnom = 10 kΩ at +25 °C; steepness β = 3977 (+25...+85 °C)
- Accuracy: enhanced accuracy ± 0.2 % in range 0...+75 °C, in the rest ± 1 %
- Measuring part housing: PVC; dimensions 4,5 x 90 mm
- Cable of two wire with PVC insulation: standard lengths - 0,1 m; 1,5 m; 3 m; 6 m
- Protection class: IP54
- Fastening with rubber sleeve and / or flange holder according to the drawing (see drawing above)
LoRa-Log-Meter is a wireless data logging system based on LoRaWAN communication technology. It is designed to collect data from LoRaWAN devices such as sensors, interfaces, and meters that monitor environmental, technological and industrial process parameters and transmit data packets to a LoRaWAN gateway.
Collected data is processed and stored in the gateway, and can be accessed via a web browser.
- Compatible with Synetica and others LoRaWAN devices: analog inputs (4–20 mA, 0–20 mA, 0–10 V), temperature sensors, pulse inputs (SO, NC/NO contacts) and others
- Individual alarm notifications based on specific sensors or contacts
- Alarm notifications via email and SMS
- Logging and review of errors and communication issues
- Remote access to the LoRa-Log-Meter system via 4G LTE, Wi-Fi, or LAN (Ethernet)
- Dynamic data visualization in graph (curve) format via a web browser
- Data export in CSV and PNG formats
- Password-protected user interface
- No subscription required for the gateway or sensors
- Remote configuration of data transmission intervals for devices via a web browser
- Communication range from sensor to gateway:
- 15 km Outdoors (in plain sight)
- 50–200 meters indoors or up to 7–8 walls*
- LoRaWAN devices powered by: 2 × AA 3.6 V lithium batteries or 5 V USB power
The LoRa-Log-Vape system, using LoRaWAN communication technology, is designed for detecting "vaping" and cigarette smoke. Sensors capture environmental parameters and, upon detecting an event, send a notification to the LoRaWAN receiver (gateway). The data is collected and processed in the receiver and can be viewed on a web page.
The LoRa-Log-Vape registration system consists of a wireless LoRaWAN sensor receiver and wireless Synetica “vape” sensors ENL-IAQ-Vape.
[Awaiting translation]
- Temperature sensor AUREGIS TJ-1-TE for temperature measurement from -40°C to 105°C
- Water-resistant – protection class IP68, fully cast in thermoplastic rubber
- Good properties in extreme freezing-melting conditions
- Датчик температуры AUREGIS ТJ-2 с минеральной изоляцией
- Предназначен для измерения температуры в диапазоне -50°C до 400°C - RTD датчикам Pt100, Pt1000 и от -50 °C до 1150 °C - термопарам
- Возможны исполнения по требованиям заказчика
- Temperature sensor TJ-B with pipe mounting
- Measuring range: -30 to 180, 250, 400°C
- Sensor type: RTD (Pt100, Pt1000), TC (K, J)
- Accuracy: A or B class / cl. 2
- Output: RTD (Pt100, Pt1000), TC (K, J), 4...20 mA, 4...20 mA +HART, 0...10 V, RS-485, IO-LINK
- Measuring part: Plate by pipe
- Material: Stainless steel AISI304 (1.4301)
- Connection head
- Type: B
- Protection class: IP65
- Extension tube
- Material: Stainless steel AISI304 (1.4301)
- Diameter: Ø 10 mm
- Length: 10; 50 mm, or according to request
- Straps: 2 pcs., not included
- Probe for process tube: Ø 15 - 40 mm
- Temperature sensor AUREGIS TJ-DIN for temperature measurement
- 35 mm DIN rail mounting
- Measuring range: -50...+70°C
- Sensor type: Pt100, Pt1000, Ni100, Ni1000, others
- Electrical connection:
- A transmitters with output: 4…20 mA, 4...20 mA +HART, 0…10 V, RS-485 or IO-LINK
- 2-wire, 3-wire, a contact terminal
- Measuring range: -40…80 °C
- Operating temperature: -40…80 °C
- The sensor can be distanced, meaning the TJ-O can be equipped with the following external temperature sensors: TJ-1, TJ-2, TJ-4, TJ-S
- Sensor tube:
- Material: Stainless steel AISI304 (1.4301)
- Diameter: Ø6 mm
- Length: 25 mm
- Mounting box:
- Material: Polystyrene
- Dimentions: 64,4x 88,4x 42,2mm
- Protection class: IP65
- The design could be changed according the requirements and drawings of the customer
- The temperature sensor TJ-PL12 is designed for measuring temperature ranging from -50°C to 400°C
- The design could be changed according the requirements and drawings of the customer
- Measuring range: -50°C ... 400°C
- Датчик температуры ТJ-S с соединительным кабелем. Предназначен для измерения температуры в диапазоне -50°C до 400°C.
- Возможны исполнения по требованиям заказчика
- Тип сенсора: PT100, PT1000, K, J
- Temperature sensor TJ-S (with cable, angled), designed for temperature measurement from -25 to +180 °C
- Various versions are available we also produce sensors according to client’s requests
- Sensor type: Pt100, Pt1000, K, J, PTC, NTC
- The temperature sensor TJ1-TTP is inextricably connected to the cable, it is designed for measuring the temperature ranging from -30 °C to 400 °C
- Various sizes are available depending on customer requirements and drawings
- Sensor type: termocouple K, J
- Temperature indicator TI-N20, TI-N24 for temperature measurement from -30 to +800 °C
- Various temperature sensor construction types are available
- Temperature indicator TI-N20/5, TI-N24/5 for temperature indication
- Various temperature sensor constructions are available: Pt100, Pt1000; NTC, PTC, termopora K, J
- The purpose of the test chamber is to measure the airtightness of doors which are in the frame of chamber at set pressure
- Air is driven into the chamber with a ventilator which is controlled by an AC drive
- The intake flow rate is measured by CS Instruments VA420 flow rate meter (0-480 m3/4)
- The pressure in chamber is measured with DPT series differential pressure transmitter
- The temperature in chamber is measured in 11 points
- All data is logged and visualized in logger and computer (via IGSS software)
- Thermocouple commutatotr TK with cold junction compensation for thermocouple measurement output (in turns) to one output
- Connecting that output to measuring device or indicator enables the monitoring of thermocouples in turns