- Inputs: 4x external sensors + 1x internal temperature sensor
- 3x Thermocouple type B, J, N, S, T external temperature sensor
- Measuring range: according to the connected thermocouple
- Accuracy: ± 0,4 °C
- Resolution: 0,1 °C
- 1x PT1000 external temperature sensor
- Measurement range: -200...+260 °C
- Accuracy: ± 0.2 °C (± 0,2 %, when temperature is in range of +100...+260 °C)
- Resolution: 0,1°C
- Internal temperature sensor
- Measuring range: -30…+70 °C
- Accuracy: ± 0,4 °C
- Resolution: 0,1 °C
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: adjustable 1 s...24 h
- Local alarms via LED indication, on LCD screen and acoustically by built-in beeper
- Data can be transferred to PC via USB-C interface
- Calibration certificate included
- Ambient temperature: -20...+70 °C
- Supply: lithium ion 3,6 V AA battery
- Protection class: IP20
- Warranty: 3 years
- Sensor for remote temperature monitoring over the Internet (Ethernet interface)
- Webserver function
- Ideal for server, air conditioning, HVAC, warehouse, museum and factory temperature monitoring
- Remote alarm (meter sends an e-mail when the set temperature range is breached)
- Archive in CSV format
- MODBUS TCP protocol
- Calibration certificate included
- 3 year warranty
- Measurement range of external sensor: -200...+600 °C
- Operating temperature: -30...+80 °C
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 2 s
- Communication protocol: WWW, ModbusTCP, SNMPv1, SOAP, XML
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Protection class: IP30
- Calibration certificate included
Data recorder with printer T-PRINT G0221E, G0241, designed for transportation temperature measurement.
Models:
T-PRINT G0221E – with printer,
T-PRINT G0241 – with printer and RS-232 output.
Complies with EN 12830, Class 1 and EN 13486, Class 1 standards for food transporation.
Appliance: food, pharmacy, flower, animal and other goods transportation temperature measurement. Designed to be mounted in driver’s cabin.
Temperature recorder with printer T-PRINT G0841, designed for transportation temperature measurement.
Models:
T-PRINT G0841 – with printer
T-PRINT G0841M – with integrated GSM modem
T-PRINT G0841MW – with integrated GSM modem and wireless output
T-PRINT G0841W – with wireless output
Complies with EN 12830, Class 1 and EN 13486, Class 1 standards for food transporation.
Appliance: food, pharmacy, flower, animal and other goods transportation temperature measurement. Designed to be mounted in driver’s cabin.
The TJ-S temperature sensor is permanently connected to a cable and designed for measuring temperatures from -50°C to 400°C.
Various cable lengths are available.
- Sensor type: PT100, PT1000, NTC, Thermocouples K, J
- Measuring range: -50…+400 °C
- Operating temperature:
- -30...+70 °C (PVC isolation)
- -50...+180 °C (Silicone isolation)
- -50...+400 °C, kabelio -50...+250 °C (Teflon isolation)
- -50...+400 °C, kabelio -50...+400 °C (Fiberglass isolation)
- Cable and connection: 2, 3, 4 wire
- Sensor tube:
- Material: Stainless steel 316 (1.4401)
- Diameter: Ø4 mm
- Length: 120 mm
- Input (configurable): TC, RTD, mV, resistance and potentiometer
- Output: Modbus RTU / ASCII Slave device over RS-485
- 1500 Vac 3-ways Galvanic Isolation
- High accuracy
- Remotely configurable over RS-485
- EMC compliance (CE mark)
- Mounting in B-type head
- Easy implementation in existing PLCs and SCADA systems
- Operating temperature: -40...+85°C
- Supply voltage: 18...30 VDC
Temperature transducer with 0...10 V output is built in a durable watertight case. Built-in precise temperature sensor. Output temperature range is user adjustable. Calibration certificate is included.
Temperature transducer with 0...10 V output is built in a durable watertight case. To be used with an external Pt1000 temperature probe. Output temperature range is user adjustable. Calibration certificate is included.
- Temperature measurement range: -20...+60 °C
- Humidity measurement range: 0...100 %RH
- CO2 concentration measurement range: 0...5000 ppm
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: 1 s...24 h
- Internal sensors
- Local alarms via LED indication, on LCD screen and acoustically by built-in beeper
- Data can be transferred to PC via USB-C interface
- Calibration certificate included
- Ambient temperature: -20...+60 °C
- Supply: 5200 mAh LiIon battery
- Protection class: IP20
- Warranty: 3 years
- Measures ambient temperature, humidity, pressure
- Calculates dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy
- Measuring ranges: -30...+80 °C, 0...100 %RH, 600...1100 hPa
- Output: Ethernet
- Optional connection to WiFi network via tiny wireless router TL-WIFI
- Webserver
- Measurement interval: 2 s
- Alarm protocols: E-mail, SNMP Trap, Syslog
- Supply: 9...30 VDC
- Calibration certificate included
- Protection class: IP30
- Temperature measurement range: -20...+60 °C
- Humidity measurement range: 0...100 %RH
- Pressure measurement range: 600...1100 hPa
- CO2 concentration measurement range: 0...5000 ppm
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: 1 s...24 h
- Internal sensors
- Local alarms via LED indication, on LCD screen and acoustically by built-in beeper
- Data can be transferred to PC via USB-C interface
- Calibration certificate included
- Ambient temperature: -20...+60 °C
- Supply: 5200 mAh LiIon battery
- Protection class: IP20
- Warranty: 3 years
Temperature, humidity, pressure, CO2 regulators, 3 binary inputs, RS-485, RS-232 interfaces, Ethernet and 2 relay outputs.
Temperature, humidity, pressure, CO2 transducers Pxxxx, Txx1x. LCD display.
- Wide temperature range: -10...+1200 °C
- 320 x 240 and 640 x 480 infrared resolution
- 9 or 60 Hz models available
- Sighting: IR-Fusion technology (thermal and visible sighting) for easy alignment and added detail on blended images
- Remote motorized focus
- Multiple field interchangeable lens options available
- GigE Vision interface
- LAN/Ethernet with PoE for communication with the thermal imager provides access to Ethernet, Web server and ThermoView Software
- I/O alarming capabilities
- ThermoView software for industrial automation applications
- Ambient temperatures to 200 °C with high temperature enclosure
- Air purge and accessories available
- Rugged housing, IP67 rated
- Thermocouple commutatotr TK with cold junction compensation for thermocouple measurement output (in turns) to one output
- Connecting that output to measuring device or indicator enables the monitoring of thermocouples in turns
The sensor consists of a replaceable insert, a ceramic protective tube (thermowell) and an aluminium connection head (depends on model) where a programmable temperature transmitter with 4-20 mA output can be installed.
- Temperature measuring range: 0… +1800 °C
- Usable areas: Blast furnaces, regenerating air heaters, industrial heating installations, heat generation
- Standard protection tube material: mullite C610 (Al2O3 60%), Ceramic C799 (99.7% Al2O3)
- Gastight process connection: (to 0.1 MPa / 1 bar)
- Optionally the head can be installed with a local temperature display (DANWdie-LED)
- ATEX and EAC Ex versions
- For specific model design please look picture below ↓: TT438, TT440, TT441, TT442, TT443, TT444
- Measurement range: -40…+180 °C
- Type: J / K / N / T / E
- Self-adhesive tape
- Thermocouple tolerance (accuracy), cable length and insulation can be chosen by demand (see datasheet)
- Optional: temperature transducer (4...20 mA / 0...10 V / HART / Profibus PA / Fieldbus)
- Optional: connector
They are used to regulate the power delivered to the receiver, where this power is proportional to the input control signal. They are used in automation control systems where smooth control of receiver power is required for resistive or resistive-inductive loads. Typical applications for power controllers: heaters, industrial furnaces (annealing, quenching, drying, etc.), dryers, plastics processing equipment, industrial sealing machines, glass production industry, industrial heating systems (matting and lining of pipelines), load transformers.
- Three-phase power controller (phase angle load control)
- Control input: DC voltage 0...10 V DC or current 4...20 mA
- SCR output (thyristors)
- Load current 25...80 A
- Max. load voltage 530 V AC (three-phase)
- Dielectric strength 4 000 Vrms (opto-isolation)
- MOV protection (built-in varistor)
- Mounting on heatsinks
- Recognitions, certifications, directives: RoHS, REACH, CE, EAC
- Display: LCD 8 digits, 7 mm; LED 6 digits, 7 mm.
- Calculation frequency: Min. 30 Hz / 20 Hz (type 3), max. 7,5 kHz
Totalizing counter Type 634 – “MINI I”.
- Display 6 or 7 digit, 4mm
- Protection class IP65
- PD51-A transducer/repeater, designed for conversion of RS232 interface to industrial RS485
- This enables to increase device number in the system and extend its range
- TOR-1 transformer oil tester is designed to detect the mass fraction of dissolved water in insulating mineral oils the viscosity of which does not exceed 70 mm2 / s (cSt) at the temperature of 50 °C
- Operating range of relative value aw (active water): 0…1
- Operating range of dissolved water content measurement: 0….500 ppm
- Precision at 20 °C ± 0.02 aw (0…0.9 aw) ± 0.03 aw (0.9…1 aw)
- Operating medium temperature: 0…55 °С
- Measured temperature of oil displayed on screen
- Measurement results can be printed out using an integrated printer
- LCD-panels displays the moisture and temperature of tested oil
- Power supply: 220 V a.c
- Easy use for oil testing in the field near the transformer
- Universal measuring inputs, it can be used for controlling of temperature (RTD, thermocouple) and other physical values
- Colored TFT display presentation of measured values (numerical values, bar graph, meter, graph)
- Control algorithms On-Off; PID; 12 segmental adjustment program
- Interfaces: USB, RS485 (MODBUS-RTU) and Ethernet (100Base-T, TCP / IP protocols: Modbus-TCP, HTTP, SMTP)
- Internal webserver, information about the active channel, measuring parameters and the status of the regulation, requires access
- Available alarm sound and visual, status outputs and alarm notification e-mail
- Write data in a standard text file located in the internal controller memory (4GB) FAT with the possibility of editing in spreadsheets such as Microsoft Excel
- Selection of PID parameters for each output
- The possibility of creating inter-channel type mathematical and logical operations: the difference, average, sum, bigger, smaller measurement
- Function digital inputs (BIN) to changes modes associated outputs, retransmission of measurements
- Free software for data processing and device programming
- Controller is destined to control the temperature and other physical quantities like pressure, humidity, level
- Three optional outputs (0/4...20 mA ± 0,2 %, 0...10 V ± 0,2 %, 0/5 V, relay voltage output)
- Universal input for RTDs, thermocouples and analog signals
- Configuration parameters via keys or an optional RS-485 Modbus and free eCon software
- The controller has three alarms, which can be assigned to each output
- The output signals are galvanic isolated from the input signals and power supply
- Selection of PID parameters for any unit, or auto-tuning
- Protection class from frontal side: IP30, from terminal side: IP20
The RE4X series controllers have a wide range of process control options and versions. Programmable inputs for standard signals, signal difference measurement between channels, control algorithms ON / OFF, PID, soft start and Fuzzy logic. Remote control with SCADA system through RS-485. The required output types can be selected during ordering (relays, SSR, analog).
Main features:
- Sampling rate (5 times / second)
- 1 input: TC and RTD sensors; standard signals 0 / 4…20 mA and 0…10 V
- 2 input: 0 / 4…20 mA and 0…10 V
- Binary input for changing the function of the controller and SP switching
- Outputs: relays - NO, SSR; analog - 0 / 4…20 mA and 0…10 V
- Galvanically isolated transducer and sensors power supply 24 V d.c. 25 mA
- Programmable digital filter
- Hardware and software security before changing settings
- Alarm for breaking the control loop
- Supply: 90…264 V a.c. or 11…26 V a.c. / d.c.
- Protection class: IP65
The RE12S Universal PID Controller is an advanced and versatile device designed for precise process control in various industrial applications. With adaptive, auto, and self-tuning PID as well as ON-OFF control capabilities, the RE12S ensures optimal performance in maintaining desired setpoints. It features a dual LED display, capacitive touch keypad, and supports up to 128-step profiling for complex control requirements. The unit's robust communication options, including RS485 MODBUS RTU, allow seamless integration into existing systems, enhancing both functionality and connectivity.
- Control algorithm: Adaptive, Auto, Self-tune PID, ON-OFF
- Input: Thermocouple (J, K, T, R, S, C, E, B, N, L, U, W, Platinel II), RTD (PT100), - 5…56mV, 0…10V, 0…20mA
- Alarm Outputs 3x: Multiple settings including deviation high/low, absolute high/low, band, sensor break
- Profile Controller: Up to 128 steps
- Special Modes: Heat-Cool PID, Auto/Manual, Single point ramp/soak, Soft start
- Communication: RS485 MODBUS RTU
- Power Supply: 90...270 VAC / DC (50/60Hz)
- Display: 4+4 digit, 7 segments
- Ambient temperature / humidity: 0…+50 °C / < 85%RH
- Dimensions: 52 x 52 x 76 mm
- In PD24 converter are used 2 interfaces (USB, RS232) - galvanically isolated
- USB interface (type A) – destined for the device communication with the computer
- RS-232 interface - destined for the communication with devices from the object side
- PD24 is programmer of LUMEL products to configure settings using eCon software
- Compliance with the standard USB 1.1 and USB 2.0
- Data transmission rate up to 115.2 kbps
- Support virtual serial port (COM)
- Device supplied from USB port and from the RS-232 (TTL) side
- Set includes 1,5 m data transmission cable with RJ12 plugs to configure LUMEL products
- External dimension: 62 x 25 x 20 mm
- In PD20 converter are used 2 interfaces (USB, RS485) - galvanically isolated
- USB interface (type A) – destined for the device communication with the computer
- RS-485 interface - destined for the communication with devices from the object side
- Compliance with the standard USB 1.1 and USB 2.0
- Data transmission rate up to 115.2 kbps
- Support virtual serial port (COM)
- Bi-directional data transmission (half duplex)
- Device supplied from USB port
- External dimension: 76 x 25 x 20mm
- Converter does not interfere into the structure of data transmission and is compatible with many industrial communication protocols
SV23 Sensor help customers monitor spaces where cameras cannot be deployed and get insight into environmental conditions that cameras cannot detect. From protecting school bathrooms against bullying and vaping to gathering real-time insight into air quality conditions like carbon dioxide levels.
- Measurement objects:
- Vape index – for vape smoke detection, range: 0…100
- PM2.5 - concentration of particulate matter, range: 0…10000 μg/m3
- TVOC index, range: 0…500
- Motion detection – FoV (field of view): 120 °
- Noise – range 20…120 dB
- CO2 (carbon dioxide) – range: 0…40000 ppm
- AQI (Air quality Index) - range: 0…500
- Temperature – range: -5…+45 °C
- Humidity – range: 0…95 % (non-condensing)
- Cloud Storage: up to 365 days
- Connectivity: RJ-45 cable connector for Network / PoE powering IEEE 802.3af
- Receive alerts for offline sensor and device tampering
- Operating temperature range: -5…+45 °C
- For toluene, xylene, ethanol, etc.
- Default calibration toluene
- Stable long-life metal-oxide sensor
- Range 0...100 % LEL
- Resolution 3 ppm LEL
- Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
- Default alarm set-points 20 % / 50 % LEL
- Remote probe option
- For toluene, xylene and ethanol
- Default calibration toluene
- Stable long-life metal-oxide sensor
- Range 0...100 % LEL
- Resolution 0,1 % LEL
- Outputs 2 relays with switch-over contacts
- Default alarm set-points 10 % / 25 % LEL
- Visual and acoustic alarms
- For toluene, xylene and ethanol
- Default calibration toluene
- Long-life metal-oxide sensor
- Range 0...100 % LEL (0...1 % vol) toluene
- Resolution 3 ppm toluene
- Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
- Default alarm set-points 20 % / 50 % LEL
- Acoustic alarm
- For toluene, xylene, ethanol, etc.
- Default calibration toluene
- Long-life metal-oxide sensor
- Range 0...100 % LEL
- Resolution 3 ppm toluene
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Remote probe option
- For toluene, xylene, ethanol and 2-propanol
- Default calibration toluene
- Stable long-life metal-oxide sensor
- Range: 0...100 % LEL or 0…500 ppm
- Resolution 0,1 % LEL or 1 ppm
- Outputs: 2 relays with switch-over contacts
- Acoustic and visual alarms
- Photo ionization detector
- Detected vapors: acetone, ethanol, toluene, xylene, etc.
- Standard calibration: isobutylene
- Range: 0...40 / 0...200 ppm (isobutylene)
- Resolution: 1 / 1 ppb
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -40...+65 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Metal-oxide gas sensor
- Detected vapors: acetone, ethanol, toluene, xylene, etc.
- Standard calibration: toluene
- Range: 0...100 % LEL (flammable range) / 0...1000 ppm (toxic range)
- Resolution: 0,1 % LEL / 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -40...+70 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
- Universal datalogger with 4 inputs for voltage, current, logic and pulse signals.
- Multilogger can be installed permanently to Ethernet network or work as a portable device.
- Measured values can be viewed on a web browser, as well as stored and downloaded for later analysis.
- Calibration certificate included.
- 3 rechargeable AA batteries with a power adapter, wall holder and USB cable are included in the delivery.
- Open collector transistor alarm output.
The TSF400-0 is a compact water-leak detector designed for early detection of water presence on floors, trays, or inside equipment enclosures. It operates from a wide 4.5–26 VDC supply and provides an N-channel open-drain output for direct connection to PLCs, controllers, alarm modules, or building-automation systems.
Applications:
Leak detection in server rooms, UPS rooms and telecom shelters
HVAC drip trays, cooling/condensation lines
Under-floor and raised-floor monitoring
Domestic and commercial flood-alert systems
Specifications:
Operating temperature range: 0...50 °C
Ingress protection: IP65
Cable length: 3 m
- 1-Wire interface
- Temperature measurement range: -20...+60 °C
- Accuracy: ±0.4°C (in -10 to +60°C range); ±0.6°C (in -20 to +60°C range)
- Humidity measurement range: 10...90 % RH
- Accuracy: ±3.0%RH (in 20 to 80 %RH range); ±5.0%RH (in 10 to 90 %RH range)
- Protection class: IP54
- Resolution: 12 bits for temperature and humidity
- Long-term stability
- Warranty: 3 years
- Input: 4x external temperature probes (Pt1000)
- Temperature measurement range: -90…+260 °C
- Accuracy: 0,2 in the range -90…+100
- Resolution: 0,1 °C
- Simple sensor connection to existing WIFI network (standard: IEEE 802.11 b/g/n)
- Measured values can be sent to the internet storage COMET Cloud or COMET Database
- Communication protocols: HTTP(S), SMTP, Modbus TCP, HTTP POST, HTTP GET (JSON, XML)
- Alarm signalization: e-mail, acoustic, LED, SMS - additional order
- Measuring interval: 1 s
- Sending interval to COMET Cloud: adjustable 5 min. to 12 hours
- Calibration certificate of manufacturer included
- Operating temperature: -30…+60 °C
- Supply: 5,0…5,4 VDC USB-C connector
- Protection class: IP30
- Temperature measurement range: -20…+60 °C
- Humidity measuring range: 0…95 % RH
- Dew point measuring range: -60…+60 °C
- CO2 measuring range: 0…5000 ppm
- Atmospheric pressure measuring range: 700…1100 hPa
- Simple sensor connection to existing WIFI network (standard: IEEE 802.11 b/g/n)
- Measured values can be sent to the internet storage COMET Cloud or COMET Database
- Communication protocols: HTTP(S), SMTP, Modbus TCP, HTTP POST, SNMP (v1, v2c, v3), HTTP GET (JSON, XML)
- Alarm signalization: e-mail, acoustic, LED, SMS - additional order
- Measuring interval: 1 s
- Sending interval to COMET Cloud: adjustable 5 min. to 12 hours
- Calibration certificate of manufacturer included
- Operating temperature: -30…+60 °C
- Supply: 5,0…5,4 VDC USB-C connector
- Protection class: IP30
- MA series converters reads Wired M-Bus meters and transmit the data wirelessly using the Wireless M-Bus protocol
- Reads data from up to 500 devices
- Communication: wM-BUS EN 13757-3/4:2013, complies OMS 4.0.2
- Modes: T1
- AES-128 encryption mode 5, profile A
- Automatically search wired meters and sends data
- Two internal antennas or one external antenna
- Power supply: 100…240 VAC
- Protection class: IP67
- Inputs: 2x Pt1000 and 2 x binary input (sensors are not included)
- Binary voltage input: low level < 0,4 V; high level: > 2 V; voltage applicable 0…30 V DC
- Binary voltage-free input: switched-on state < 10 kOhm; switched-off state > 300 kOhm
- Binary input IS NOT suitable for catching the „voltage applied / not applied” states
- Temperature measurement range: -200...+260 °C
- Accuracy: ± 0.2 °C (± 0,2 %, when temperature is in range of +100...+260 °C)
- GSM (GPRS) modem, (SIM card are not included)
- Measured values can be sent to the internet storage COMET Cloud
- SMS and JSON messages can be sent via GPRS data connection
- Memory: up to 500,000 values in non-cyclic mode and 350 000 in cyclic mode
- Logging interval: 1 s...24 h
- Local alarms via LED indication, on LCD screen and acoustically by built-in beeper
- Calibration certificate of manufacturer included
- Data can be transferred to PC via USB-C interface
- Ambient temperature: -20...+60 °C
- Supply: battery SONY Li-ion 5200mAh
- Protection class: IP20
- Warranty: 3 years
- Temperature measurement range: 0...+50 °C
- Humidity measurement range: 0...85 %
- Pressure measurement range: 300...1100 hPa
- CO2 concentration measurement range: 0...9999 ppm
- Operational range (in line-of-sight): up to 10 m (Bluetooth Low Energy)
- Data is sent to smartphone (Android, iOS), no need for special receiver
- Data transmission: 1, 2, 5, 10 min
- Aranet4 anti-theft wall mount is available
- Data encryption
- Supply: 2 x AA batteries
- Battery lifetime (20 °C): up to 2 years
- Operating temperature: 0...+50 °C
- Protection class: IP20
Sensor SKU: 5906660327868 (IP30)
Efento NB-IoT sensors transmit the data over cellular network (Narrowband IoT) and do not require any additional devices (router, gateway, etc.). Sensors are also equipped with Bluetooth Low Energy interface, which allows quick and easy configuration with a smartphone. Efento NB-IoT sensors can be integrated with Efento Cloud** platform or any other third party systems.
- Carbon dioxide (CO2) measurement range: 400…5000 ppm, accuracy: +/- (40 ppm + 5 % of reading)
- Atmospheric pressure measurement range: 300…1100 hPa, accuracy: absolute +/- 3 hPa in temperature 0…+65°C, relative +/- 0,12 hPa in temperature 0…+65°C
- Temperature measurement range: -15…+70 °C, accuracy: up to 0,4 °C
- Relative humidity measurement range: 0…99 % RH, accuracy 4 % in 0…80 % RH
- Communication NB-IoT bands: default B8 and B20 (others on request)
- Measurement period: 1 minutes to 18 hours (configurable by the user)
- Measurement sending interval: 5 minutes to 7 days (configurable by the user)
- Battery ensures up to 5 years of maintenance-free operation, 6300 mAh battery
- The device stores 40,000 measurements in its memory, when the memory is full, the oldest measurements are overwritten
- Possibility to integrate sensor to other third-party systems
- Operating environmental: -15…+70 °C / 0…99 % RH non-condensing
- Case IP30 protection
Sensor measures carbon dioxide (CO2) concentration, temperature, and atmospheric pressure. This device, belonging to the PRO sensor series, includes Aranet Sub-GHz ISM band radio which wirelessly transmits sensor measurements to the Aranet PRO base station.
- CO2 measurements:
- Range: 0…9999 ppm
- Resolution: 1 ppm
- Accuracy: ± (30 ppm + 3 % of reading)
- Atmospheric pressure measurements:
- Range: 300…1100 hPa
- Resolution: 1 hPa
- Accuracy: +3 hPa / -2 hPa
- Temperature measurements:
- Range: 0…50 °C
- Resolution: 0,1 °C
- Accuracy: ± 0.3 °C
- Operational range (in line-of-sight): up to 3 km
- Data transmission: 1, 2, 5, 10 min
- Data encryption
- Supply: 1 x AA battery
- Battery lifetime (20 °C): up to 8 years
- Operating temperature: -40…60 °C
- Protection class: IP67
Sensor SKU: 5905309601376 (IP30)
Efento BLE sensors transmit the data over BLE (Bluetooth Low Energy) and send data to the Efento cloud** through Efento gateway or to other third-party integration. Free mobile application let to configure the device and read the data from its memory.
- Device monitor state of relays or reed switches (1 channel for input)
- Measurement and transmission period: 5 seconds to 30 days (configurable by the user)
- Battery ensures up to 5 years of maintenance-free operation (15 min. measurement interval), 2700 mAh, 3,6 V, AA battery (replaceable)
- The device stores 40,000 measurements in its memory, when the memory is full, the oldest measurements are overwritten
- The device can be used as a stand-alone data logger or connected to the Efento gateway to view and store data in the Efento cloud
- Possibility to integrate sensor to other third-party systems
- Operating temperature / humidity: -35…+70 °C / 0…99 %
- Case IP30 protection
Sensor SKU: 5906660327714 (IP30)
Sensor SKU: 5905309600713 (IP67)
Efento NB-IoT sensors transmit the data over cellular network (Narrowband IoT) and do not require any additional devices (router, gateway, etc.). Sensors are also equipped with Bluetooth Low Energy interface, which allows quick and easy configuration with a smartphone. Efento NB-IoT sensors can be integrated with Efento Cloud platform or any other third party systems.
- Device monitor state of relays or reed switches (1 channel for input)
- Communication NB-IoT bands: default B8 and B20 (others on request)
- Measurement period: 1 minutes to 18 hours (configurable by the user)
- Measurement sending interval: 5 minutes to 7 days (configurable by the user)
- Battery ensures up to 5 years of maintenance-free operation, 6300 mAh battery
- The device stores 40,000 measurements in its memory, when the memory is full, the oldest measurements are overwritten
- Sensor's configuration can be changed remotely from the cloud or with a mobile application over Bluetooth Low Energy
- Operating temperature: -35…+70 °C
- Case IP30 protection (IP67 on request)