Multifunctional indoor climate sensor AERASGARD RFTM - LQ - PS - CO2 - Modbus with with LCD display.
- Temperature measuring range / deviation: 0…+50 °C / ± 0,2 °C at +25 °C
- Humidity measuring range / deviation: 0…100 % RH / ± 2 % RH (20…80 % RH), at 25 °C, otherwise ± 3 %
- CO2 Measuring range / accuracy: 0…5000 ppm / ± 30 ppm ± 3 % of measured value
- Particulate matter (PM) measuring range / accuracy: 0…50 μg/m³ 0…100 μg/m³ 0…300 μg/m³ 0…500 μg/m³
- Particulate matter (PM) accuracy ± 10 μg/m3 (± 10 % of measured value) at PM 2.5, ± 25 μg/m3 (± 25 % of measured value) at PM 10
- Air quality (VOC) measuring range: 0…100 %
- Data output: galvanically separated RS-485 Modbus RTU interface
- Variants: with / without LCD display
- One sensor covers about 30 m² of room area
- Power supply: 24 V ac/dc (200 mA)
- Standards: CE, EN 61 326, EMC Directive 2014/ 30/ EU, 2014/ 35/ EU
- Suitable for ATEX Zones 2 and 22
- Electrochemical gas sensor
- Range: 0...100, 0...300, 0...1000, 0...5000 ppm NH3
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+50 °C
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life pellistor (catalytic bead) sensor
- Range: 0...15% vol. (0…100% LEL)
- Resolution: 0.1% vol. or 1% LEL
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -10...+50 °C
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life photoacoustic or optical NDIR sensor
- Range: 0...10 000 ppm / 0...40 000 ppm / 0...5 % vol (0...100 % on request)
- Resolution: 1 ppm / 10 ppm / 0.01 % vol. CO2
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+60 °C; 0….100 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range: 0...300 or 0...1000 ppm
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -20...+50 °C; 0….90 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Detected gases: hydrogen, methane, acetylene, propane, butane
- Default calibration: methane CH4
- Stable long-life metal-oxide / pellistor sensor
- Range: 0...100% LEL
- Resolution: 0,1 / 1 % LEL
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+70 °C; ≤ 95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range: 0...10 / 0...200 / 0...1500 ppm
- Resolution: 0,1 / 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+50 °C; up to 100 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Detectable gases: R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R-507, R-514a, R-1234ze and similar
- Stable long-life metal-oxide sensor
- Range: 0…1000 / 0…2500 ppm
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -30...+60 °C; < 95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range: 0...100 ppm, 0...2000 ppm H2S
- Resolution: 1 ppm H2S
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+50 °C; 15…90 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life metal-oxide / pellistor sensor
- Range: 0...100% LEL CH4
- Resolution: 0,1 / 1 % LEL CH4
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+70 °C; ≤ 95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range: 0…250 ppm
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -30...+50 °C; 15…90 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life optical NDIR sensor
- Range: 0…1000 ppm
- Resolution: 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -20...+50 °C; 0…95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range: 0...25 % vol O2
- Resolution: 0,01 % vol O2
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+60 °C; 5…95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Highly sensitive Photo Ionization Detector (PID) sensor
- Detectable gases: VOCs (acetone, ethanol, toluene, xylene etc.)
- Default calibration: Isobutylene
- Range: 0…40 / 0…200 ppm isobutylene
- Resolution: 0,01 / 1 ppm
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+65 °C; 0…95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Suitable for ATEX Zones 2 and 22
- Stable long-life metal-oxide sensor
- Detectable gases: acetone, ethanol, toluene, xylene etc.
- Default calibration: toluene
- Range: 0...1000 ppm (toxic range) / 0...100% LEL (flammable range)
- Resolution: 1 ppm for toxic ranges / 0,1 % LEL for flammable range
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST)
- Operating temperature: -40...+70 °C; < 95 % RH; 0,9…1,1 atm.
- Supply: 12...36 VDC (default), 24 VAC or 230 VAC
- Flow monitor for liquid media in the range of 4…400 cm/s with analog (4…20 mA) and status output (PNP, NPN) for monitoring a flow threshold
- Ten LEDs indicate flow and contact closure
- Equipped with 2 control buttons for setting the switching point
- Available with 65 mm and 125 mm mounting depths
- Rugged design for industrial environments, IP67
- Flow sensor suitable for evaluation unit NLSW®45-6 and NLSW®45-6.1
- Thread: PG7, optional accessories available
- Material: stainless steel V4A
- Media temperature: optional up to 400°C
- Protection class sensor: IP50
- Insertion depth: 50 mm, 130 mm, 165 mm, 300 mm
- Compressive strength: 10 bar
Fluid level alarm Elcluwo 111S, designed for usage with conductometric probes for fluid level alarm and control.
Technical specifications
- One or more level control
- Switch output 2A, 250 VAC
- Probe supply from isolated ~12 V source
- Adjustable sensitivity
- Available modes – flooding, drainage, dry flow, overflooding
- Pump or valve control
- Designed for work with various probes: SKS 401, 201, 101, SW-01 and others
- Mounting on standard rail (35 mm)
Fluid level alarm Elcluwo 112S, designed for usage with conductometric probes for fluid level alarm and control, depth pump protection.
Technical specifications
- One or more level control
- Switch outputs: switching + NO 2 A / 250 VAC
- Probe supply from isolated ~12 V source
- Adjustable sensitivity
- Available modes – flooding, drainage, dry flow, overflooding
- Pump or valve control
- Designed for work with various probes: SKS 401, 201, 101, SW-01 and others
- Mounting on standard rail (35 mm)
- One or more level control
- Switch outputs: switching + 3 x NO 2 A / 250 VAC
- Probes: galvanically isolated, max. 2mA, 5V~ 100 Hz
- Adjustable sensitivity
- Available modes – flooding, drainage, dry flow, overflooding
- Pump or valve control
- Designed for work with various probes: SKS 401, 201, 101, SW-01 and others
- Mounting on standard rail (35 mm)
- Supply: 230 VAC / 24 VAC
- One or two level control
- Switch outputs – switching + 5 x NO, 2A / 250 VAC
- Probes: galvanically isolated, max. 2uA, 5V~ 100 Hz
- Adjustable sensitivity
- Available modes – filling, draining, dry flow, overflow, two/three pump control and others
- Valve or gate control
- Adapted for work with various probes – SKS 401, 201, 101, SW-01 and others
- Mounted on standard rail (35 mm)
- Supply: 230 VAC / 24 VAC
The FPI 8237 IO-Link Flush Membrane pressure transmitter impresses with an absolutely smooth and robust flush-mounted measuring diaphragm made of corrosion-resistant duplex steel 1.4462. Trafag’s proprietary thin-film-on-steel sensor technology ensures a wide temperature range and excellent long-term stability.
- Measuring range: -0,5...0,5 to 0...100 bar
- Output signal: IO-Link 1.1, COM3, min. process cycle time 1 ms, Smart Sensor Profile ED2, 2 Switching outputs PNP / NPN / Push-Pull configurable
- Accuracy at 25°C typically: ± 0.5 % FS typ.
- Measuring principle: Thin-film-on-steel
- Media temperature –10... +125 °C
- Ambient temperature: –10...+125 °C
- Protection class: IP65, IP67
- Applications: Hydraulics, Machine tools, Process technology, Food industry, Water treatment
- Portable, small dimension grain moisture meter
- The sample is ground, increasing the measurement accuracy
- External probes can be connected
- Temperature measurement accuracy: ±0,5 °C
- Moisture measurement accuracy: ±0,5 %
- Automatic temperature compensation
- Calibrated for more than 400 grain species
- 2” LCD screen
- USB connection for software updates and data transfer
- Supply: 4xAA (1,5 V), 1xCR2032 (3 V)
- Portable, small dimension grain moisture meter
- Temperature measurement accuracy: ±0,5 °C
- Moisture measurement accuracy: ±1 % (in range up to 10 %)
- Calibrated for more than a hundred grain types (the list can be extended)
- Automatic temperature compensation
- 2” LCD screen
- USB connection for software updates
- Supply: 2xAA (1,5 V, LR6)
- Portable, small dimension grain moisture meter
- The sample is ground, increasing the measurement accuracy
- Temperature measurement accuracy: ±0,5 °C
- Moisture measurement accuracy: ±0,5 %
- Calibrated for more than 400 grain types
- Automatic temperature compensation
- 2” LCD screen
- USB connection for software updates
- Supply: 1x6LF-22 (9 V)
- Portable, small dimension grain moisture meter
- The sample is ground, increasing the measurement accuracy
- Temperature measurement accuracy: ±1 °C
- Moisture measurement accuracy: ±0,5 %
- Automatic temperature compensation
- LCD screen
- Supply: 4xAA (1,5 V), 1xCR2032 (3 V)
- GA-1 is designed for grease detection in separators, basins and tanks
- Easy to install, does not need calibration
- Switch output
- Remote monitoring capability
- Wall-mounted
- Supply: 230 VAC, 50/60 Hz
- GA-2 is designed for grease detection in separators, basins and tanks
- Two sensors – one is for grease detection, other – for blockage control
- Easy to install, does not need calibration
- 2 switch outputs
- Remote monitoring capability
- Wall-mounted
- Supply: 230 VAC, 50/60 Hz
Kuhlmann Ground Thawing Blankets are durable and weatherproof, designed to thaw frozen ground and soil, pipes, and protect equipment from freezing. They also work as curing blankets for various construction purposes.
Technical specifications:
- Durable PVC materials.
- Fixed temperature (70°C).
- 2-meter power cable.
- Special sizes produced upon request.
- IP67 Class.
- In normal conditions the mat thaws up to 30 cm of soil in 24 hours - or up to 60 cm in more sandy soil/ground.
- High level detection
- Oil on water surface detection
- Designed for usage in separators, basins and tanks
- Easy to install, does not need calibration
- Reliable long-term se in harshest conditions
- Acoustic and visual alarms
- 2 switch outputs
- ATEX certified
- Wall-mounted
- Supply: 230 VAC, 50/60 Hz
- Temperature measurement range: 0...50 °C
- Humidity measurement range: 0...100 %
- Output: 2 x 0...10 V / 2...10 V / 4...20 mA
- Option: LCD display
- Option: relay output
- Option: Modbus RTU
- Supply: 24 VDC/VAC
- Operating temperature: 0...50 °C
- Protection class: IP20
- Temperature measurement range: 0...50 °C
- Humidity measurement range: 0...100 %
- Output: 2 x 0/2...5/10 VDC
- Option: LCD display
- Option: Modbus RTU
- Supply: 24 VDC/VAC
- Operating temperature: 0...50 °C
- Protection class: IP54
- Long-life metal-oxide gas sensor
- Range 0...100 % LEL H2
- Resolution 0,1 % LEL H2
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Attached or remote sensor options
- Stable long-life electrochemical gas sensor
- Range 0...100 / 0...1000 ppm H2S
- Resolution 0,1 / 1 ppm H2S
- Outputs 2 switches, 2 x 4...20 mA / 0...10 V, RS-485
- Default alarm set-points 10 / 20 ppm H2S
- Stable long-life electrochemical gas sensor
- Range 0...100 / 0...1000 ppm H2S
- Resolution 0,1 / 1 ppm H2S
- Outputs 2 x 4...20 mA / 0...10 V, RS-485
- Attached or remote sensor option
- Electrochemical gas sensor
- Range: 0...100 / 0...2000 ppm H2S
- Resolution: 0,1 / 1 ppm H2S
- Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
- Digital output: RS-485 (Modbus RTU protocol)
- Option: relay output (2 x SPST) / LCD indicator
- Option: remote sensor (default cable length is 3 m)
- Operating temperature: -40...+50 °C
- Supply: 11...30 VDC / 24 VAC or 90...265 VAC
The Kuhlmann Electro-Heat IBC Immersion Heater is an efficient solution for heating liquids in Intermediate Bulk Containers (IBCs), addressing viscosity challenges to enhance industrial productivity. Suitable for a variety of substances, it ensures consistent heating and easy liquid management. Its applications span multiple industries, including chemical processing, pharmaceuticals, food and beverage, and oil and gas. Constructed with durable stainless steel and featuring precise temperature control, this immersion heater combines performance with longevity.
Technical Specifications:
- Surface load: 2.2 W/cm²
- Power: 2000W
- Supply: 230V 1-phase
- Stainless steel tube element AISI 316L (1.4404)
- Length of element: 950mm
- Diameter of element: ø100mm
- Heated zone: 300mm
- Integrated PT100 sensor
- Minimum level of liquid during heating: 500mm (half full)
- Cable between heater and control unit: ~2800mm
- Digital controller: 0-90°C
An IBC silicone base heater efficiently heats up contents in an IBC container, making it easy to discharge viscous or semi-solid products with minimal waste. The 2700W heater can heat water from 15°C to 70°C in less than 40 hours. Kuhlmann’s durable silicone base heater fits various IBC containers and is easy to install and use. It can also be mounted with a digital temperature controller for precise temperature control.
Technical Specifications:
- Dimensions: 1035 - 851mm.
- Materials: 100% silicone.
- 1,5 meter power cord with no plugs.
- 0-150°C PT100 Sensor System temperature controller (additional product).
- Heats water from 15°C - 70°C in less than 40 hours in a fully loaded IBC Container.
idOil sensors are an integral part of the idOil oil separator alarm system and they are to be used with the idOil control units. All idOil sensors are digital and polarity free. Standard cable length is 5 m.
- idOil-LIQ high liquid level sensor
Indicates when the liquid level in the oil separator rises excessively e.g. in an outlet blockage situation. - idOil-OIL oil sensor
Detects oil and indicates when the separator’s oil storage is full. - idOil-SLU sludge sensor
Monitors the sludge layer in the oil separator and indicates when the sludge layer has reached its maximum level.
“idOil®” is an alarm system intended for monitoring liquid levels particularly in oil and sand separators. The system consists of the idOil control unit and the idOil sensors installed in the separator. The sensor cables can be extended with a cable connector or connection box. One to three digital idOil sensors of the same or different type can be connected to the control unit. The sensors can be used to monitor the following:
- High liquid level (idOil-LIQ high liquid level sensor)
- Oil layer detection (idOil-OIL oil sensor is for class IIA explosive liquids and idOil-OIL-Soil sensor is for class IIB explosive liquids)
- Sludge layer detection (idOil-SLU sludge sensor)
“idOil®” is an alarm system intended for monitoring liquid levels particularly in oil and sand separators. The system consists of the idOil control unit and the idOil sensors installed in the separator. The sensor cables can be extended with a cable connector or connection box. One to three digital idOil sensors of the same or different type can be connected to the control unit. The sensors can be used to monitor the following:
- High liquid level (idOil-LIQ high liquid level sensor)
- Oil layer detection (idOil-OIL oil sensor is for class IIA explosive liquids and idOil-OIL-Soil sensor is for class IIB explosive liquids)
- Sludge layer detection (idOil-SLU sludge sensor)
- Measurement of parameters: voltage, current, active, reactive and apparent power, cosφ, tgφ, frequency, active, reactive and apparent energy, active power 15 minutes, voltage 10 minutes
- Current and voltage harmonics analysis up to 51st (measurements available via RS-485)
- Programmable input:
- Current: 0…1 / 0…5A
- Voltage: 0…100V / 0…230V / 0…400V
- Output:
- Analog: 0/4...20 mA or 0...10 V
- Relays: 1 or 4
- Binary (OC)
- Digital output: RS-485 modbus (can be programmed through RS-485)
- Two-line LCD display
- Pulse output to measure energy consumption
- 4 alarm outputs with signaling on LED diodes, working in 7 different modes
- Conversion of any measured value into an analog signal 0/4...20 mA or 0...10V
- Protection grade: frontal side – IP65 / from terminal side – IP10
- Operating temperature: -25...23...55 °C
N19Z meter measures AC voltage and current. The meter is designed to work in 3-phase networks or 1-phase networks.
- Nominal input voltage: 300 or 600 V 1 phase / 100…500 V 3 phase
- Nominal input current: 1A or 5A
- True RMS measurement (up to 15th Harmonic)
- On site programmable PT/CT ratios
- User selectable 3ph3wire or 3ph4wire Network (for 3ph)
- Onsite selection of Auto scroll / Fixed Screen (for 3ph)
- 4 Digits 14mm ultra bright LED Display
- Protection: IP54 front / IP20 back
- Parameter Screen recall: In case of power failure, the instrument memorizes the last displayed screen
- Accuracy: ±0.5% of nominal value
The CM22 provides essential video security features in a compact form. It is a 3MP (2048x1536) camera with 10 meters of IR light range, and includes people and vehicle detection for motion search and trajectory analysis. The CM22 camera, combined with the SV23 vape detector and air quality sensor, and powered by the Verkada Command cloud computing platform, creates a powerful vape prevention and logging system.
- 30, 60 and 90 days of data retention (256…768 GB) on hardware and cloud back-up. If the connection to the Command cloud is lost, data is saved onboard and synced once the internet connection is restored
- Easy to install: no NVR, DVR, servers or port forwarding, just PoE connection
- Alerts: Camera status (offline), motion detection, people detection, vehicle detection, crowd detection, line-crossing detection, loitering detection
- Privacy: live face blur, privacy regions and audit log
- Field of view: Horizontal: 95°; Vertical: 69°; Diagonal: 130°
- Operating temperature / humidity: -10…50 °C / 0…90 %
- Connection and power input: RJ-45, PoE (IEEE 802.3af type 1)
- Certifications: FCC, ICES, RCM, VCCI, CE, UKCA, EN 50155 railway compliance, UL/cUL/IEC 62368-1, NOM
- Warranty: 5 years
Interior protection from flooding sensor CZP-103R, designed for protection of various rooms (workshops, servers, communication modules, etc.) against flooding. The sensor activates when there is water between its electrodes. Can be used in drainages and rainfall wells for protection against basement flooding. LED indication.
- Flood protection
- Alarm and control
- Supply 12...24 VDC
- Isolated ~5 V electrode supply
- Low energy consumption
- Size 19 mm x 66 mm
The Internal IBC Heater is a unique approach to heating viscous foodstuffs and chemicals within IBC Containers. It is designed to protect sensitive products, such as syrups, honey, treacle, molasses, fats and other viscous products that are difficult to process. Most products can be batched within a relatively short time, increasing efficiency and reducing down time.
Technical specifications:
- Designed for insertion into 1000 litre cubic IBC but will also fit inside most IBC configurations.
- Adjustable temperature range from 0°C to 70°C using an easy to use controller on the top of the heater.
- 230/240 Volts - up to 2.4kW power output.
- Finned, food safe heating element that is inserted into the IBC, thereby heating the contents directly.
- Fast batching ability. Unique thermodynamic core that gives even temperature distribution along the heating extrusion,
- Preventing thermal damage to the liquid contents of the IBC.
- Non-stick industrial strength Xylon coating for easy washdown.
- Carefully designed low Watt density to protect sensitive products.
- Lightweight with stainless steel handles for easy insertion and extraction.
- Even temperature distribution along the length of the heating extrusion.
- Colored LED for power cycle and status indication.
- 16 Amp blue industrial power plug.
- Protective sleeve between the base of the control unit and the neck of the IBC to prevent ingress of contaminants.
- Robust Construction:
- IP67-rated body with potentiometer control mounted under protective see-through cover.
- The product is sealed to ensure that all the connections and components are waterproof.
- Robust IP67-rated aluminum case.
- Long life heating elements.
- Input: standard 4...20 mA signal or capacitive Labkotec 3W probe
- Current output: 0/4...20 mA
- Switch outputs: 2 units
- LCD display
- Programmable using buttons
- ATEX certified
- Wall-mounted, IP65
- Supply: 230 VAC, 50/60 Hz
- High level detection
- Oil on water surface detection
- Sludge under water detection
- Designed for usage in separators, basins and tanks
- Version with GSM module available – for alarms and service reminders
- Acoustic and visual alarms
- 2 switch outputs
- ATEX certified
- Wall-mounted
- Supply: 230 VAC, 50/60 Hz
- Output: switch
- Application: level sensing for solids
- Supply: 24 VDC / 220 VAC
- Sensitivity setting: 3 positions
- Rotation speed: 1 per minute
- Operating temperature: -20...+70 °C
- Operating pressure: up to 0,8 bar
- Material: body – plastic, other component – stainless steel
- Protection class: IP65
- Weight: 1 kg