Astronomical digital clocks RAT-TPA1B are applied for switching on and off the lightning or other electrical receivers in accordance to sunset and sunrise with an option to program a night break, which means a temporary switching off of the receivers for savings purposes
- 52 programs, holiday mode
- Automatic summer/winter digital clockover
- Automatic transfer of weekdays
- Sealable cover of the front panel, easy setting by 4 buttons
- Backlighted LCD display (can be turned off)
- 10-year power reserve (internal lithium battery which can protect real time clock and all the settings when the electric power supply is off)
- Number and type of contacts: 1 CO
- Rated load: 16 A / 250 V AC
- Direct mounting on 35 mm rail mount acc. to EN 60715
- Compliance with standards EN 60730-1, EN 60730-2-7, Directive RoHS
Multifunction astronomical digital clocks RDT-TPA2 are applied for switching on and off the lightning or other electrical receivers in accordance to sunset and sunrise.
- 80 programs (astronomical and annual), holiday mode, random mode
- Automatic summer/winter digital clockover
- Automatic transfer of weekdays
- Sealable cover of the front panel, easy setting by 4 buttons
- Backlighted LCD display (can be turned off)
- 10-year power reserve (internal lithium battery which can protect real time clock and all the settings when the electric power supply is off)
- Number and type of contacts: 2 CO (each channel can be assigned an individual program)
- Rated load: 16 A / 250 V AC
- Direct mounting on 35 mm rail mount acc. to EN 60715
- Compliance with standards EN 60730-1, EN 60730-2-7, Directive RoHS
Applications:
Surge protection for 2 pair lines or 4 single lines with common reference potential in the data, signal and communication systems: 0-20 mA, 4-20 mA current loop, TTY 4-20 mA, TTY, TTL, V24 (RS232C), high-frequency transmission system.
Specifications:
- ANSI / IEEE C62.41 category: B, C
- Rated operating voltage Un 24 V DC
- Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
- Rated load current at 25°C IL 1 A
- Nom. discharge current (8/20 μs) In 10 kA
- Max. discharge current (8/20 μs) Imax 20 kA
- D1 current impulse (10/350 μs, per line) 2,5 kA
- Voltage protection level Up:
- at In, C2 (8/20 μs, line-line, line-PG) ≤ 55 V
- at C3, 1 kV/µs (line-line, line-PG) ≤ 48 V
- Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019
Applications:
surge protection for 2 pair lines of closed circuit (loops) in the data, signal and communication systems: 4-20 mA current loop, analog/digital communication, RS485, RS422 (V11) interface, high-frequency bus system, 2 wires video transmission system.
Specifications:
- ANSI / IEEE C62.41 category: B, C
- Rated operating voltage Un 24 V DC
- Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
- Rated load current at 25°C IL 1 A
- Nom. discharge current (8/20 μs) In 10 kA
- Max. discharge current (8/20 μs) Imax 20 kA
- D1 current impulse (10/350 μs, per line) 2,5 kA
- Voltage protection level Up:
- at In, C2 (8/20 μs, line-line) ≤ 55 V
- at In, C2 (8/20 μs, line-PG) ≤ 500 V
- at C3, 1 kV/µs (line-line) ≤ 48 V
- at C3, 1 kV/µs (line-PG) ≤ 600 V
- Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019
Applications:
- For protecting low voltage equipment against lightning and surge damages
- For installation in conformity with the lightning protection zones concept at LPZ 0-1
- Designed according to IEC 61643-11:2011
Specifications:
- Category IEC / EN / VDE: class II+III / type 2+3 / C+D
- Max. continuous operating voltage Uc 275 V AC
- Nom. discharge current (8/20 μs) In 10 kA
- Max. discharge current (8/20 μs) Imax 20 kA
- Voltage protection level Up ≤ 1,5 kV
- Max. backup fuse 125 A
They are used to regulate the power delivered to the receiver, where this power is proportional to the input control signal. They are used in automation control systems where smooth control of receiver power is required for resistive or resistive-inductive loads. Typical applications for power controllers: heaters, industrial furnaces (annealing, quenching, drying, etc.), dryers, plastics processing equipment, industrial sealing machines, glass production industry, industrial heating systems (matting and lining of pipelines), load transformers.
- Single-phase power controller (phase angle load control)
- Control input: DC voltage 0...10 V DC (RSR92-..V..) or current 4...20 mA (RSR92-..I..)
- SCR output (thyristors)
- Load current 25...80 A
- Max. load voltage 280, 530 V AC (single-phase)
- Dielectric strength 4 000 Vrms (opto-isolation)
- MOV protection (built-in varistor)
- Mounting on panel or on heatsinks
- Recognitions, certifications, directives: RoHS, REACH, CE, EAC
- Self-operating signal lamps (optic signaling of AC/DC voltage presence in 1-phase network via lighting of one non-replaceable LED)
- LED colors: green, red, yellow
- Cover - modular, width 17,5 mm
- Direct mounting on 35 mm rail mount acc. to EN 60715
- Applications: in low-voltage systems (130…260 V)
- Compliance with standards: EN 62094-1, EN 61000-4-2, 3, 4, 5, 6, 11
- Recognitions, certifications, directives: RoHS, CE, EAC, UKCA
RSP-E25-... is a Class I+II SPD for surge and lightning protection of low-voltage power supply systems, especially in high-risk exposure areas or building entrances in LPZ 0-2 (IEC 62305-4), protecting against damage caused by direct or nearby lightning strikes; suitable for use in main distribution boards.
- IEC / EN / VDE category: Class I+II / Type 1+2 / B+C
- Application: main distribution boards (MB)
- Power networks: TT, TN-S, TN-C
- Protection modes: L-N, N-PE
- Protective elements: MOV, MOV+GDT
- Enclosure: modular (replaceable module)
- Mechanical status indicator: green/red flag
- Compliant with standards: IEC/EN 61643-11:2011, IEC 60364-4-53, IEC 62305, CE, RoHS
They are used to regulate the power delivered to the receiver, where this power is proportional to the input control signal. They are used in automation control systems where smooth control of receiver power is required for resistive or resistive-inductive loads. Typical applications for power controllers: heaters, industrial furnaces (annealing, quenching, drying, etc.), dryers, plastics processing equipment, industrial sealing machines, glass production industry, industrial heating systems (matting and lining of pipelines), load transformers.
- Three-phase power controller (phase angle load control)
- Control input: DC voltage 0...10 V DC or current 4...20 mA
- SCR output (thyristors)
- Load current 25...80 A
- Max. load voltage 530 V AC (three-phase)
- Dielectric strength 4 000 Vrms (opto-isolation)
- MOV protection (built-in varistor)
- Mounting on heatsinks
- Recognitions, certifications, directives: RoHS, REACH, CE, EAC
- Self-operating signal lamps (optic signaling of AC/DC voltage presence in 3-phase network – 3(N) 400 / 230 V via lighting of one non-replaceable LED)
- LED colors: green, red, (red, yellow, green)
- Cover - modular, width 17,5 mm
- Direct mounting on 35 mm rail mount acc. to EN 60715
- Applications: in low-voltage systems (400 / 230 V)
- Compliance with standards: EN 62094-1, EN 61000-4-2, 3, 4, 5, 6, 11
- Recognitions, certifications, directives: RoHS, CE, EAC, UKCA