Overload protector 05-04. Designed to protect pressure measuring devices from too fast or too big step change of pressure. This device blocks bigger than expected pressure until system gets back into normal state. Technical specificationsMaximum working pressure: 400 bar;Process connection: 1/2 BSP MxF, 1/2 NPT MxF, 1/4 BSP MxF, 3/8 BSP MxF, 3/8 NPT MxF;Material of construction: AISI 316 SS;Operating temperature: -40°C .. 120°C;  05-04 datasheet [EN] ..

Applications:

Surge protection for 2 pair lines or 4 single lines with common reference potential in the data, signal and communication systems: 0-20 mA, 4-20 mA current loop, TTY 4-20 mA, TTY, TTL, V24 (RS232C), high-frequency transmission system.

Specifications:

  • ANSI / IEEE C62.41 category: B, C
  • Rated operating voltage Un 24 V DC
  • Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
  • Rated load current at 25°C IL 1 A
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • D1 current impulse (10/350 μs, per line) 2,5 kA
  • Voltage protection level Up:
    • at In, C2 (8/20 μs, line-line, line-PG) ≤ 55 V
    • at C3, 1 kV/µs (line-line, line-PG) ≤ 48 V
  • Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019

Applications:

surge protection for 2 pair lines of closed circuit (loops) in the data, signal and communication systems: 4-20 mA current loop, analog/digital communication, RS485, RS422 (V11) interface, high-frequency bus system, 2 wires video transmission system.

Specifications:

  • ANSI / IEEE C62.41 category: B, C
  • Rated operating voltage Un 24 V DC
  • Max. continuous operating voltage Uc 33 V DC / 23,3 V AC
  • Rated load current at 25°C IL 1 A
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • D1 current impulse (10/350 μs, per line) 2,5 kA
  • Voltage protection level Up:
    • at In, C2 (8/20 μs, line-line) ≤ 55 V
    • at In, C2 (8/20 μs, line-PG) ≤ 500 V
    • at C3, 1 kV/µs (line-line) ≤ 48 V
    • at C3, 1 kV/µs (line-PG) ≤ 600 V
  • Compliance with standards: EN 61643-11:2012, EN 61643-21:2001+A1:2009+A2:2013, EN 61643-31:2019

Applications:

  • For protecting low voltage equipment against lightning and surge damages
  • For installation in conformity with the lightning protection zones concept at LPZ 0-1
  • Designed according to IEC 61643-11:2011

 

Specifications:

  • Category IEC / EN / VDE: class II+III / type 2+3 / C+D
  • Max. continuous operating voltage Uc 275 V AC
  • Nom. discharge current (8/20 μs) In 10 kA
  • Max. discharge current (8/20 μs) Imax 20 kA
  • Voltage protection level Up ≤ 1,5 kV
  • Max. backup fuse 125 A

RSP-E25-... is a Class I+II SPD for surge and lightning protection of low-voltage power supply systems, especially in high-risk exposure areas or building entrances in LPZ 0-2 (IEC 62305-4), protecting against damage caused by direct or nearby lightning strikes; suitable for use in main distribution boards.

  • IEC / EN / VDE category: Class I+II / Type 1+2 / B+C
  • Application: main distribution boards (MB)
  • Power networks: TT, TN-S, TN-C
  • Protection modes: L-N, N-PE
  • Protective elements: MOV, MOV+GDT
  • Enclosure: modular (replaceable module)
  • Mechanical status indicator: green/red flag
  • Compliant with standards: IEC/EN 61643-11:2011, IEC 60364-4-53, IEC 62305, CE, RoHS