  • Suitable for ATEX Zones 2 and 22
  • Highly sensitive Photo Ionization Detector (PID) sensor
  • Detectable gases: VOCs (acetone, ethanol, toluene, xylene etc.)
  • Default calibration: Isobutylene
  • Range: 0…40 / 0…200 ppm isobutylene
  • Resolution: 0,01 / 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+65 °C; 0…95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life metal-oxide sensor
  • Detectable gases: acetone, ethanol, toluene, xylene etc.
  • Default calibration: toluene
  • Range: 0...1000 ppm (toxic range) / 0...100% LEL (flammable range)
  • Resolution: 1 ppm for toxic ranges / 0,1 % LEL for flammable range
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST)
  • Operating temperature: -40...+70 °C; < 95 % RH; 0,9…1,1 atm.
  • Supply: 12...36 VDC (default), 24 VAC or 230 VAC
  • For toluene, xylene, ethanol, etc.
  • Default calibration toluene
  • Stable long-life metal-oxide sensor
  • Range 0...100 % LEL
  • Resolution 3 ppm LEL
  • Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
  • Default alarm set-points 20 % / 50 % LEL
  • Remote probe option
  • For toluene, xylene and ethanol
  • Default calibration toluene
  • Stable long-life metal-oxide sensor
  • Range 0...100 % LEL
  • Resolution 0,1 % LEL
  • Outputs 2 relays with switch-over contacts
  • Default alarm set-points 10 % / 25 % LEL
  • Visual and acoustic alarms
  • For toluene, xylene and ethanol
  • Default calibration toluene
  • Long-life metal-oxide sensor
  • Range 0...100 % LEL (0...1 % vol) toluene
  • Resolution 3 ppm toluene
  • Outputs 2 relays, 2 x 4...20 mA / 0...10 V, RS-485
  • Default alarm set-points 20 % / 50 % LEL
  • Acoustic alarm
  • For toluene, xylene, ethanol, etc.
  • Default calibration toluene
  • Long-life metal-oxide sensor
  • Range 0...100 % LEL
  • Resolution 3 ppm toluene
  • Outputs 2 x 4...20 mA / 0...10 V, RS-485
  • Remote probe option
  • For toluene, xylene, ethanol and 2-propanol
  • Default calibration toluene
  • Stable long-life metal-oxide sensor
  • Range: 0...100 % LEL or 0…500 ppm
  • Resolution 0,1 % LEL or 1 ppm
  • Outputs: 2 relays with switch-over contacts
  • Acoustic and visual alarms
  • Photo ionization detector
  • Detected vapors: acetone, ethanol, toluene, xylene, etc.
  • Standard calibration: isobutylene
  • Range: 0...40 / 0...200 ppm (isobutylene)
  • Resolution: 1 / 1 ppb
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -40...+65 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC
  • Metal-oxide gas sensor
  • Detected vapors: acetone, ethanol, toluene, xylene, etc.
  • Standard calibration: toluene
  • Range: 0...100 % LEL (flammable range) / 0...1000 ppm (toxic range)
  • Resolution: 0,1 % LEL / 1 ppm
  • Analog output: 2 x 4...20 mA / 0...10 V (user-settable)
  • Digital output: RS-485 (Modbus RTU protocol)
  • Option: relay output (2 x SPST) / LCD indicator
  • Option: remote sensor (default cable length is 3 m)
  • Operating temperature: -40...+70 °C
  • Supply: 11...30 VDC / 24 VAC or 90...265 VAC